5.3.5 HEATING DELAY REGULATION.
5.3.6 HEATING MAXIMUM POWER REGULATION.
The boiler has two different maximum power: one for sanitary and one lower for heating (absolute maximum
heating power).
The absolute maximum heating power is set by parameter 2 30. This parameter must be verified and
eventually modified only and exclusively in the case of a gas change.
UTLET PRESSURE ABSOLUTE MAXIMUM HEATING POWER
(mbar)
G20
G31
24 kW CF
11
31.2
28 kW CF
10.4
34.2
24 kW FF
12.2
35.5
30 kW FF
12.3
35.3
32 kW FF
9.4
34.5
35 kW FF
10.8
33
To adjust the heating power at the heating circuit there is maximum heating power regulation (between
minimum heating and absolute maximum heating power).
5.3.7 TABELLA RIEPILOGATIVA GAS
ALTEAS X 24
FF
GENUS X
24 FF
ALTEAS X 30
FF
GENUS X
30 FF
ALTEAS X 32
FF
GENUS X
32 FF
ALTEAS X 35
FF
GENUS X
35 FF
G20
G31
G20
G31
G20
G31
G20
G31
Lower Wobbe index (15°C, 1013 mbar) ( MJ/m
3
)
MJ/m
3
45,67
70,69
45,67
70,69
45,67
70,69
45,67
70,69
Gas inlet pressure
mbar
20
37
20
37
20
37
20
37
Gas Burner Pressure
Maximum d.H.W.
mbar
12,2
35,5
12,3
35,3
10,8
33,0
10,8
33,0
Maximum heating-absolute
(parameter
230
)
mbar
12,2
(100)
35,5
(100)
12,3
(100)
35,3
(100)
9,4
(57)
34,5
(82)
10,8
(100)
33,0
(100)
Minimum
mbar
2,3
6,8
2,4
7,0
2,1
6,8
2,1
6,8
Soft light
(Parameter
220
)
mbar
4,5
(43)
6,8
(5)
5,6
(48)
7,0
(5)
4,9
(44)
8,6
(54)
4,9
(44)
8,4
(54)
Maximum heating power adjustment - Paraìmetro
231
50
71
47
71
75
80
44
69
Ignition delay - Parameter
235
automatic
Main Burner jets
nr.
11
13
16
16
Ø burner jets
mm
1,32
0,8
1,32
0,8
1,32
0,78
1,32
0,78
Gas flow max/min
(15°C, 1013 mbar)
(nat - m3/h) (GPL - kg/h)
max D.H.W
2,73
2,00
3,17
2,33
3,65
2,68
3,65
2,68
max C.H
2,73
2,00
3,17
2,33
3,44
2,52
3,65
2,68
min
1,16
0,85
1,38
1,01
1,59
1,17
1,59
1,17
- Regulation carried out on parameter 2 36
This boiler has a regulation that allows to change the delay
time between the heating request and the burner ignition
choosing between 0 and 7 minutes. This regulation is carried
out on parameter 2 36 .
- - Regulation carried out on parameter 2 31
This boiler has a regulation that allows to change the
maximum heating power by means of parameter 2 31.