8.3.1 Menù 0 : Network
8.3.2 Menù 2 : Boiler parameter
Menù
Sub
Menù
Parameter
Function
Range
Default
setting
0
2
BUS NETWORK
0
2
0
Network presence in the bus
(only visualization)
/
0
4
USER INTERFACE
0
4
0
Zone to be set by display
1: heating zone 1
2: heating zone 2
3: heating zone 3
1
0
4
1
Backlight time (min)
1 ÷ 10 ; 24h
10min
0
4
2
Thermoregulation button
deactivation
0: OFF
1: ON
0
Menù
Sub Menù
Parameter
Function
Range
Default
setting
2
0
GENERAL
2
0
0
DHW setpoint temperature
36 ÷ 60
/
2
1
FREEPARAMETERS
2
1
4
Boiler circulator type
0: Standard efficiency
1: High efficiency
1
2
2
GENERAL
2
2
0
Slow ignition as % of the
maximum heating power
0 ÷ 100
See gas
table
2
2
2
Fan modulation
0: disabled
1: enabled
0
2
2
4
Thermoregulation
0: disabled
1: enabled
0
2
2
5
Heating delay restart
0: disabled
1: 10 seconds
2: 90 seconds
3: 210 seconds
0
2
2
6
Conventional boiler
configuration
0: Monothermic open chamber
1: Monothermic open chamber VMC
2: Monothermic sealed chamber fan fix
speed
3: Monothermic sealed chamber fan
modulating speed
4 Bithermic open chamber
5 Bithermic sealed chamber
Depend on
the boiler
version
2
2
8
Boiler version
0: combi
1: Storage with NTC (tank)
2: only heating or storage with
thermostat
3: micro-storage
Depend on
the boiler
version
2
2
9
Boiler nominal power
0 ÷ 100 kW
Depend on