38
settings - adjustment - problem identi cation menus
menu
sub-menu
parameter
Description range
factory
setting
32
SPECIAL SETTINGS
320Anti-legionella Function - NOT ACTIVE Only for boiler with storage inside
321Solar Confi guration Type 0 = Nothing or single coil Natural
circulation
1 =
Single coil Forced circulation
2 = Double coil
0 Select 1 or 2 only if the Solar Kit is
installed
322Electrical Mixing valve
Only with Solar Kit is installed
323Collector Delta T pump ON
324Collector Delta T pump OFF
325Minimum Collector Temperature Pump ON
326Kollectorkick
327Recooling Function
328Gas storage set point Delta
329Collector Frost protection Temperature
4 ZONE 1 PARAMETERS
4 0 ZONE 1 SET TEMPERATURE
400
Set Day Temperature Zona 1
from 16 to 30 (°C) 19
only active when the BUS device is
connected
401
Set Night Temperature Zona 1
from 16 to 30 (°C) 16
402
Fix temperature central heating
from 35 to85 (°C) 70 To set only with Fixed Flow Temperaure of
Thermoregulation (see 421)
4 1 Service code 222
Rotate encoder clockwise to select
code 234 and press M
ENU/OK
4 2 SET ZONE 1
420Zone 1 Temperature range
DO NOT MODIFY
0= Low Temperature
1= High Temperature
ONLY FOR SERVICE
Active only with MGZ/MCM Kit
421Select Type of Thermoregulation 0 = Fixed Flow Temperature
1 = Basic Thermoregulation
2 = Room Temperature only
3 = Outdoor Temperature only
4 =
Room +
Outdoor
Temperature
1 To enabled thermoregulation press Auto
button. The display show the symbol.
422Zone 1 Slope from 0_2 to 3_5 1_5
Only enabled when an outdoor sen-
sor is installed
When an outdoor sensor is used, the boiler
calculates the most suitable delivery
temperature, taking into account the
outside temperature and type of system.
The type of curve should be selected
in correspondence with the projected
temperature of the system and the
nature of the dispersions present in the
structure.
For high-temperature systems, one of
the curves depicted in the chart may be
chosen.
1.0 - 1.5 = Standard System
2.0 - 3.5 = Convector Radiators
Note: The Outdoor Sensor should only be
used when the boiler is used for central heating
only.
temperatura di mandata all’impianto
alta tempertaura
temperatura esterna
30
40
50
60
70
80
90
100°C
10
2.5 3.0 3.5 2.0
1.5
1.2
1.0
5 0 -5 -10 -15 -20 °C
External temperature
High temperature
Flow Temperature