39
settings - adjustment - problem identi cation menus
menu
sub-menu
parameter
Description range
factory
setting
423
Parallel curve shift
Zone 1 Off set from - 20 to + 20 0
To adapt the heating curve to the system requirements, shift the curve in parallel so that the calculated fl ow temperature
is modifi ed, in addition to the room temperature.
By accessing this parameter and turning knob “5” (Figs 1 and 2 - page 4), the curve can be shifted in a parallel manner.
The value is indicated on the display, from -20 to +20.
424Room sensor Infl uence to calculate the
set-point temperature - Thermoregulation
enabled-
from 0 to 20 20
If set to = 0 the room temperature doesn’t infl uence the calculation of the set-point.
If set to = 20, the room temperature has the maximun infl uence to calculate the set-
point
-
only active when the BUS device is connected
425Maximum Central Heating Temperature Zone1 from 40 to 82 (°C) 82
426Minimum Central Heating Temperature Zone 1 from 40 to 82 (°C) 40
43
DIAGNOSTICS
430
Room Temperature Zone 1 -
only active when the BUS device is connected
431
Flow Temperature Zone 1 -
only active when the BUS device is connected
432Zone 1 Heat Request 0 = OFF 1 =ON
433Zone 1 Pump status 0 = OFF 1 =ON Active only with MGZ/MCM Kit
44
ZONE 1 DEVICES
440Zone 1
Pump control
0 = OFF 1 =ON Active only with MGZ/MCM Kit
5 ZONE 2 PARAMETER
5 0 ZONE 2 SET TEMPERATURE
500
Set Day Temperature Zona 2
from 16 to 30 (°C) 19
only active when the BUS device is
connected
501
Set Night Temperature Zona 2
from 16 to 30 (°C) 16
502
Fix temperature central heating
from 35 to85 (°C) 70 To set only with Fixed Flow Temperaure of
Thermoregulation (see 521)
5 1 Service code 222
Press +/- to select code 234 and press
M
ENU/OK
5 2 SET ZONE 2
520Zone 2 Temperature range
DO NOT MODIFY
0= Low Temperature
1= High Temperature
ONLY FOR SERVICE
Active only with MGZ/MCM Kit
521Select Type of Thermoregulation 0 = Fixed Flow Temperature
1 = Basic Thermoregulation
2 = Room Temperature only
3 = Outdoor Temperature only
4 =
Room +
Outdoor
Temperature
1 To enabled thermoregulation press Auto
button. The display show the symbol.
522Zone 1 Slope from 0_2 to 3_5 1_5
Only enabled when an outdoor sen-
sor is installed
When an outdoor sensor is used, the boiler calculates the most suitable delivery
temperature, taking into account the outside temperature and type of system.
The type of curve should be selected in correspondence with the projected
temperature of the system and the nature of the dispersions present in the
structure. For high-temperature systems, one of the curves depicted in the chart
may be chosen.
1.0 - 1.5 = Standard System
2.0 - 3.5 = Convector Radiators
Note: The Outdoor Sensor should only be used when the boiler is used for central heating only.
see graph previous page
prameter 4 2 2