18
B063
IS THE BURNER
ALIGHT?
YES
NO
YES
YES
BOILER
WORKING?
YES
NO
NO
NO
NO
YES
5-CHECK/REPLACE P.C.B. (CBM2)
4-C
HECK/REPLACE P.C.B. (CBM2)
4 - C
HECK/REPLACE
P.C.B. (CBM2)
1 - C
HECK/REPLACE IGNITION
ELECTRODES
2 - CHECK THE CABLES
3 - CHECK SPARK GENERATOR
4 - CHECK IGNITION ELECTRODE
CABLES
1 - CHECK POWER SUPPLY TO
THE GAS VALVE
2 - CHECK OPERATION OF THE
GAS VALVE
3 - REPLACE THE GAS VALVE
1 - CHECK IF THE FLAME
ELECTRODE
2 - CHECK THE SOFT-LIGHT
GAS PRESSURE
3 - CHECK/REPLACE DETECTION
ELECTRODE
STRIKES THE DETECTION
PRESS THE RESET
BUTTON
IS THE
AIR PRESSURE SWITCH
ACTIVATED?
CHECK
P ON PRESSURE
TEST POINT
DOES
THE SPARK
SEQUENCE
START?
HAS THE
BOILER SAFETY
SHUTDOWN BEEN
ACTIVATED?
1 - CHECK EXHAUST DISCHARGE
2 - CHECK VENTURI AND TUBES
3 - CHECK THE FAN EFFICIENCY
4 - REPLACE FAN
1 - CHECK AIR PRESSURE
SWITCH CABLE
2 - CHECK/REPLACE AIR
PRESSURE SWITCH
3 - CHECK/REPLACE P. C. B .
(CBM2)
B
P mbar0.5
P 0.5 mbar
IS
THERE STILL
A PROBLEM?
NORMAL
OPERATION
NORMAL
OPERATION
NO
YES
FAULT LIST POSSIBLE CAUSES
1
2
3
4
5
NOISEY OPERATION
NOISEY OPERATION
DECREASE/INCREASE OF HEATING CIRCUIT
PRESSURE
DECREASE/INCREASE OF HEATING CIRCUIT
PRESSURE
REPEATED SHUTDOWNS
REPEATED SHUTDOWNS
REPEATED OPERATION OF SAFETY THERMOSTAT
REPEATED OPERATION OF SAFETY THERMOSTAT
INSUFFICIENT RADIATOR TEMPERATURE
INSUFFICIENT RADIATOR TEMPERATURE
- MAIN HEAT EXCHANGER FAULTY OR BLOCKED
WITH LIME
-SCALE DEPOSITS
- LOW HEATING SYSTEM WATER PRESSURE
- CHECK GAS PRESSURES
- CHECK HEATING THERMOSTAT
- CHECK FAN
- CHECK PUMP
- MAIN HEAT EXCHANGER FAULTY OR BLOCKED
WITH LIME-SCALE DEPOSITS
- LOW HEATING SYSTEM WATER PRESSURE
- CHECK GAS PRESSURES
- CHECK HEATING THERMOSTAT
- CHECK FAN
- CHECK PUMP
- CHECK FOR LEAKS ON THE HEATING CIRCUIT
- FAULTY FILLING LOOP
- FAULTY EXPANSION VESSEL
- CHECK FOR LEAKS ON THE HEATING CIRCUIT
- FAULTY FILLING LOOP
- FAULTY EXPANSION VESSEL
- FAULTY DETECTION ELECTRODES
- CHECK GAS PRESSURES
- CHECK FLAME DETECTION ELECTRICAL CIRCUIT
- FAULTY DETECTION ELECTRODES
- CHECK GAS PRESSURES
- CHECK FLAME DETECTION ELECTRICAL CIRCUIT
- FAULTY HEATING THERMOSTAT
- FAULTY OVERHEAT THERMOSTAT
- PRESENCE OF AIR IN THE HEATING CIRCUIT
- CHECK BURNER PRESSURES
- CHECK EXCHANGER FLUEWAY
- FAULTY HEATING THERMOSTAT
- FAULTY OVERHEAT THERMOSTAT
- PRESENCE OF AIR IN THE HEATING CIRCUIT
- CHECK BURNER PRESSURES
- CHECK EXCHANGER FLUEWAY
- CHECK HEATING THERMOSTAT
- CHECK BY-PASS
- CHECK GAS PRESSURE
- CHECK HEATING THERMOSTAT
- CHECK BY-PASS
- CHECK GAS PRESSURE
FC002Ac

Other manuals for Ariston microSYSTEM 10 RFFI

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Ariston microSYSTEM 10 RFFI and is the answer not in the manual?

Ariston microSYSTEM 10 RFFI Specifications

General IconGeneral
BrandAriston
ModelmicroSYSTEM 10 RFFI
CategoryBoiler
LanguageEnglish

Related product manuals