1X-X3 Operation Manual 15
Fire alarm indications will be on as usual if the extinguishing event that caused
the release was not a start manual call point activation. Fire routing indications, if
configured, are shown in the usual manner, linked to the fire alarm event.
The control panel buzzer sounds continuously.
Faults
Faults are indicated with a flashing General Fault LED and an active fault
indication LED corresponding to the feature or device with a fault.
The control panel buzzer sounds intermittently.
Note: Contact your installation or maintenance contractor to solve all reported
faults. Some faults can prevent or disable the extinguishing event. See
Extinguishing event preventedon page 12 for more information.
Disablements
A disabled extinguishing event is indicated by a steady General Disable LED
and a steady yellow Preactivation LED.
Disabled zones are indicated by a steady General Disable LED and a steady
yellow Zone LED.
Disabled extinguishing sounders (and sounder outputs linked to the
preactivation or released states) are indicated by a steady General Disable
LED and a steady yellow Extinguishing Sounders On LED.
Disabled fire sounders are indicated by a steady General Disable LED and a
steady yellow Fire Sounders LED.
Disabled fire routing is indicated by a steady General Disable LED and a
steady yellow Fire Routing LED.
Disabled expansion boards are indicated by a steady General Disable LED
and a steady Expansion I/O Fault/Disabled.
Disabled actuators are indicated by a steady General Disable LED and a
steady yellow Released LED.
Disabled safety door monitoring is indicated by a steady General Disable LED
and a steady Door Fault/Disabled LED.
Disabled extinguishing agent flow monitoring is indicated by a steady General
Disable LED and a steady yellow Extinguishing Agent Flow LED.
Disabled extinguishing agent pressure monitoring is indicated by a steady
General Disable LED and a steady yellow Low Pressure LED.
Disabled extinguishing released optical warning panels or signs are indicated
by a steady General Disable LED and a steady yellow Optical Panel On LED.
Disabled start, hold, or abort extinguishing manual call points are indicated by
a steady General Disable LED and a steady yellow LED for MCP Start, MCP
Hold, or MCP Abort.
There is no audible indication.