EasyManua.ls Logo

Aritech 1X-X3 - Page 22

Aritech 1X-X3
38 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
16 1X-X3 Operation Manual
Note: Some disablements can prevent or disable the extinguishing event. See
Extinguishing event preventedon page 12 for more information.
Tests
Zone tests are indicated by a steady General Test LED and a steady yellow
Zone LED.
Extinguishing sounder tests are indicated by a steady General Test LED and
a steady yellow Extinguishing Sounders On LED.
Fire sounder tests are indicated by a steady General Test LED and a steady
yellow Fire Sounders LED.
Fire routing tests are indicated by a steady General Test LED and a steady
yellow Fire Routing LED.
Actuator tests are indicated by a steady General Test LED and a steady
yellow Released LED.
Extinguishing agent flow monitoring tests are indicated by a steady General
Test LED and a steady yellow Extinguishing Agent Flow LED.
Extinguishing agent pressure monitoring tests are indicated by a steady
General Test LED and a steady yellow Low Pressure LED.
Extinguishing released optical warning panel or sign tests are indicated by a
steady General Test LED and a steady yellow Optical Panel On LED.
Start, hold, or abort extinguishing manual call point tests are indicated by a
steady General Test LED and a steady yellow LED for MCP Start, MCP Hold,
or MCP Abort.
There is no audible indicator.
WARNING: Risk of death or serious injury. Disconnect the extinguishing agent
actuator from the control panel before you issue the actuator output test
command. When you confirm the test command, the actuator output is activated
immediately.

Other manuals for Aritech 1X-X3

Related product manuals