Chapter 3: Configuration and commissioning
118 2X-A Series Installation Manual
To configure the output group delay:
1. Select Field setup from the Main menu, and then select Activation
configuration.
2. Select the output group type to configure (Sounder, Fire routing, etc.).
3. Select Group_n, and then select ALL (to configure common delay settings for
all output groups of the type selected) or select the output group number (to
configure custom delay settings for a single output group of the type
selected).
4. Select Active, and then select YES (to confirm output group activation in case
of an alarm) or NO (to deactivate the output group).
5. Select Delay and enter the required delay in minutes and seconds.
The maximum delay value for sounder, fire routing, and fire protection output
groups is 10 minutes. The maximum delay value for program output groups is
16 minutes and 40 seconds.
6. If required, enter a warning delay (in minutes and seconds) for sounder output
groups in applications using warning tones (second stage sounders).
A warning delay is only observed if the corresponding warning time is also
configured (see “Warning timeon page 123 for more information on this
option). The maximum warning delay value is 10 minutes.
7. Press F4 (Enter), and then press F1 (Back).
8. Press F1 (Save), F3 (Apply), F4 (Discard), or F2 (Exit).
Remember to apply saved settings from the Main menu.
Once a delay has been configured, it must be enabled.
Configured delays are only activated for alarms activated by a detector. Alarms
activated by a manual call point ignore any configured delays.
Configured delays can be enabled or disabled by sensitivity mode programming
(day/night mode), remote equipment by means of a programmed input, or the
user interface delay buttons.
By default, the control panel does not process delays when operating in night
mode. Remember that night mode can be activated by the day/night mode
schedule, the holiday calendar, or by remote equipment. For specific
applications, a delay in night mode can be configured if required. See “Additional
day/night mode settingson page 55.
Use these options to configure, for example, activation of sounders and fire
routing with 2 minute delay for any zone in alarm in the fire network inside the fire
alarm panel zone range.

Table of Contents

Other manuals for Aritech 2X-A Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Aritech 2X-A Series and is the answer not in the manual?

Aritech 2X-A Series Specifications

General IconGeneral
BrandAritech
Model2X-A Series
CategorySmoke Alarm
LanguageEnglish

Related product manuals