Chapter 5: Technical specifications
2X-A Series Installation Manual 141
LCD specifications
Display type
240 x 128 dot graphic LCD (monochromatic)
LCD dimensions (L x W)
83 x 44 mm (active area)
Backlight type
LED style
Backlight colour
White
Communication port specifications
Ethernet
Ethernet 10/100BaseT port (10 Mbps)
Note: For increased security, we recommend against using
Ethernet for remote connection to the control panel via the
Internet.
TCP/IP
IPv4
USB host port
USB 2.0, type A connector
USB
device port USB 2.0, type B connector
Fire network specifications
Maximum distance between
two control panels
1.2 km
Maximum default capacity
32 loops and 32 nodes
Communication protocol
Proprietary protocol based on RS-485
Input and output specifications
Input and output overview
Configurable
outputs
General fire
outputs
General fault
outputs
24V AUX
output
Configurable
inputs
One
-loop panel 2 Class B
1 Class A
2 (see note) 2 (see note) 1 2
Two
-loop panel 4 Class B
2 Class A
2 (see note) 2 (see note) 1 2
Two
-loop panel with
loop board
8 Class B
4 Class A
2 2 1 2
Repeater panel
0 2 2 1 2
Note: 1 supervised output and 1 potential-free relay.

Table of Contents

Other manuals for Aritech 2X-A Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Aritech 2X-A Series and is the answer not in the manual?

Aritech 2X-A Series Specifications

General IconGeneral
BrandAritech
Model2X-A Series
CategorySmoke Alarm
LanguageEnglish

Related product manuals