MULTIPLE EXPANSIONS
Several Battery Boxes can be connected in a cascade to ensure prolonged autonomy. The connections should be made
as shown here below:
WARNING (only for single UPS): No more than one UPS may be connected to each Battery Box or to more than
one Battery Box connected in a cascade.
SETTING THE RATED BATTERY CAPACITY SOFTWARE CONFIGURATION
Having installed one or more BATTERY BOXES, the UPS must be set up to update the rated capacity value (total Ah of
batteries inside the UPS + external batteries).
This setting should be made using the advanced configuration software UPSTools, present on the CD-ROM provided
with the UPS or directly from the control panel of the UPS.
Installing and running UPSTools:
¾ Follow the installation and operating instructions given in the software manual present in the UPSTools folder of
the CD-ROM.
Making the setting from the display
Set the rated battery capacity following the indications given in the “USE” chapter.
EXTERNAL TEMPERATURE PROBE
This NON ISOLATED input may be used to measure the temperature inside a remote Battery Box.
The special kit provided by the manufacturers must be used: any methods not conforming to specifications
may cause faults or breakdowns in the equipment.
To install, connect the cable included in the special kit to the "EXT BATTERY TEMP PROBE" connector (see "View of
the UPS Connections" ref. 3).
After installation, enable the external temperature measuring function using the advanced configuration software
UPSTools present on the CD-ROM provided with the UPS.