- 100 -
¾ Lock: indicates that the UPS is locked, a lock is normally preceded by an alarm signal and, due to their gravity,
causes the inverter to be turned off and the load to be powered via the bypass line (this procedure is excluded
for locks caused by serious and persistent overloads and for a lock caused by a short circuit).
CODE DESCRIPTION
L01 Incorrect auxiliary power supply
L02 One or more internal cables disconnected
L03 Phase 1 input fuse broken or input relay locked (will not close)
L04 Phase 2 input fuse broken or input relay locked (will not close)
L05 Phase 3 input fuse broken or input relay locked (will not close)
L06 BOOST stage overvoltage positive
L07 BOOST stage overvoltage negative
L08 BOOST stage undervoltage positive
L09 BOOST stage undervoltage negative
L10 Static bypass switch fault
L11 output undervoltage
L14 inverter overvoltage
L17 inverter undervoltage
L20 Direct voltage at output of inverter or Sine wave inverter distorted
L23 Overload at output
L26 Short circuit at output of Phase1
L29 output fuse broken or output relay locked (will not close)
L34 Heat sink 1 overtemperature
L35 Heat sink 2 overtemperature
L36 Heat sink 3 overtemperature
L37 Battery charger overtermperature
L38
Temperature probe of heat sink 1 faulty
L39 Temperature probe of heat sink 2 faulty
L40 Temperature probe of heat sink 3 faulty
L41 Temperature probe of battery charger faulty
L42 BOOST battery 1 fuse blown
L43 BOOST battery 2 fuse blown
L44 BOOST battery 3 fuse blown