EasyManua.ls Logo

Arteche CA-36 - Page 17

Default Icon
22 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3
High Voltage Instrument Transformers | CA/UT/KA
User Manual - Annex III
It is recommended that the test be carried out at a voltage of
10 kV AC.
If the device has a tanδ tap, it is recommended to perform the
test through this tap.
HV (UST) test for transformers with tanδ tap (Fig. 3):
The test must be performed in UST (Ungrounded Specimen
Test) mode.
The (HV) power cable of the measuring equipment must be
connected to the primary terminal (A).
The neutral connection of the primary (N*) must be
disconnected from the ground and connected to the guard
cable.
The measurement cable must be connected to the tanδ tap,
which should be previously disconnected from the ground.
The corresponding secondary terminals at the end of each
secondary winding must be connected to each other, and to
earth.
Warning: At the end of the test, the tanδ should be grounded
and the contact should be verifi ed.
HV (GST) test for transformers without tanδ tap (Fig. 4):
The test must be performed in GST ( Ground Specimen Test)
mode.
The (HV) power cable of the measuring equipment must be
connected to the primary terminal (A).
The neutral connection of the primary (N*) must be
disconnected from the ground and connected to the guard
cable.
The measuring cable of the measuring instrument must be
connected to the ground terminal, directly at the base of the
instrument.
The corresponding secondary terminals at the end of each
secondary winding must be connected to each other, and to
earth.
INDUCTIVE VOLTAGE TRANSFORMERS/
Fig. 3
A
Ta n δ tap
LV
measuring
cable
Fig. 4
A
* The N or P2 terminal can be located inside the secondary terminal box on the side of the box or on the outside of the tank.
N N
LV
measuring
cable
Guard
Wire - P2
Guard
Wire - P2

Related product manuals