Ascon Tecnologic - e34B - OPERATING INSTRUCTIONS - PAG. 16
Parameter Description Range Def. Note
30
ddL
Display Lock during defrost
oF Not active;
on Active at last measure;
Lb Active with label (dEF during defrost and PdF at defrost).
oF
31
dcd
Defrost activation time for continuous compressor
operating
oF Disabled;
-1 ÷ -59 (min) ÷ 1 ÷ 99 (h)
oF
32
dde
Max. defrost duration
oF Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
20
33
ddp
Pre-defrost time length for dH output
oF Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
oF
34
dpd
Post-defrost time length for dH output
oF Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
oF
35
dtd
Compressor delay after defrost (drainage time)
oF Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min)
20
36
ddt
Defrosting Type
EL
Electrical heating/stop compressor;
in
Hot gas/reverse cycle;
no
Without compressor output condictioning;
Et
Electrical heating with evaporator temperature control.
EL
37
ddC
Defrosting starting mode
rt Real time intervals;
ct ot output on time intervals;
cS Defrost every ot switching OFF (+ rt intervals);
cL Do not use.
rt
38
ddi
Defrosting interval
oF Function disabled;
-1 ÷ -59 (min) ÷ 1 ÷ 99 (h).
oF
39
dSd
Delay first defrost after power-on
oF Defrost at power-on;
-1 ÷ -59 (min) ÷ 1 ÷ 99 (h).
oF
40
ddd
Dynamic Defrost Percentage reduction
0 ÷ 100% 0
41
dEi
Defrosting interval for evaporator probe error
oF Function disabled;
-1 ÷ -59 (min) ÷ 1 ÷ 99 (h)
6
42
dEE
Lengh of defrost cycle for evaporator probe error
oF Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
10
43
Ftn
Fan time activation with ot output (compressor) OFF
oF Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
5
44
FtF
Fan time deactivation with ot output (compressor) OFF
oF Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
oF
45
FFL
High temperature fan deactivation - 99.9 ÷ 999 °C/°F 10.0
46
FLF
Low temperature fan deactivation - 99.9 ÷ 999°C/°F -99.9
47
FdF
Differential fan control 0.0 ÷ 30.0°C/°F 1.0
48
FFE
Fan status during defrost oF - on oF
49
FFd
Fan delay after defrost
oF Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
oF
50
PP1
ot output delay at switching ON
oF Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
oF
51
PP2
ot output delay after switching OFF
oF Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
oF
52
PP3
Min. time between two ot output switching ON
oF Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
oF
53
Pod
Outputs delay at power ON
oF Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
oF
54
AAy
Temperature Alarm 1 type
1
Absolute for Pr1 with label Hi or Lo;
2
Relative to Pr1 with
label Hi or Lo;
3
Absolute for Au with label Hi or Lo;
4
Relative to
Au
with
label Hi or Lo;
5 Absolute for Pr1 with no label;
6 Relative to Pr1
with no label;
7
Absolute for Au with no label;
8 Relative to Au
with no label.
1
55
AHA
High temperature Alarm threshold
oF Function disabled;
-99.9 ÷ +999°C/°F.
oF
56
ALA
Low temperature Alarm threshold
oF Function disabled;
-99.9 ÷ +999°C/°F
oF
57
AAd
Temperature Alarms Differential 0.0 ÷ 30.0°C/°F 1.0
58
AAt
Temperature Alarms Delay
oF Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
oF