Ascon Tecnologic - e34B - OPERATING INSTRUCTIONS - PAG. 17
Parameter Description Range Def. Note
59
AtA
Alarms memory
oF
Alarm memory disabled;
on
Alarm memory enabled;
oF
60
APA
Temperature Alarms delay at power ON
oF Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
2
61
AdA
Temperature Alarms delay
after defrost
and
unlock display delay after defrost
oF Function disabled;
-1 ÷ -59 (min) ÷ 1 ÷ 99 (h).
1
62
AoA
Open Door Alarm Delay
oF Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
3
63
oo1
OUT1 function
oF No function;
ot
Temperature control (compressor);
dF Defrost;
Fn Fans;
Au Auxiliary;
At/-t Silenceable alarm;
AL/-L Not silenceable Alarm;
An/-n Stored Alarm;
on ON when the instrument is ON;
HE Heating (Neutral zone control)
L1
Showcase light with ECO function (ON with SP, OFF with SPE);
L2 Interior light (OFF with door closed, lit with door open);
dH Pre and post defrost resistance output.
ot
64
oo2
OUT2 function dF
65
oo3
OUT3 function Fn
66
oo4
OUT4 function L1
67
obu
Buzzer function mode
oF Function disabled;
1 Active for alarms only;
2 Active for key pressed only;
3, 4 Active for alarms and key pressed.
3
68
oFo
Auxiliary output function
oF Function disabled;
1 Control output ot delayed;
2 Manual activation by key.
oF
69
otu
Time relative to auxiliary output
oF Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 99 (min).
oF
70
tUF
/ Key Function
oF No function;
1 Eco Mode direct selection
(+ turn OFF the showcase light, if configured);
2 Switch ON/Switch OFF (Stand-by) the controller.
1
71
tFb
/ Key Function
oF No function;
1 Enable key to control the light (L1 and Au with Fo = 2).
1
72
tLo
Keyboard lock function delay
oF Function disabled;
-1 ÷ -59 (s) ÷ 1 ÷ 30 (min).
oF
73
tEd
Set Point change procedure
0 Disabled;
1 Active Set Point Direct change between limits SH... SE;
2 Active Set Point Direct selection between SP1, SP2 and SP3
with and keys.
2
74
tPP
Password to Access Parameter set up
oF Function disabled;
001 ÷ 999.
oF
75
tas
Seroal Communications Address 0 ÷ 255. 1
76
tdu
Filter to suppress the display of increasing temperature
variations lower than 0.1°
oF Function disabled;
0.1 ÷ 20.0 s
oF
77
tdd
Filter to suppress the display of decreasing temperature
variations lower than 0.1°
oF Function disabled;
0.1 ÷ 20.0 s
oF
78
ULU
Low mains alarm
oF Function disabled;
9 ÷ 27 (V x 10).
oF
79
UHU
High Mains alarm
oF Function disabled;
9 ÷ 27 (V x 10).
oF
80
UUd
Mains alamrs delay
oF Function disabled;
-01 ÷ -59 (s) ÷ 01 ÷ 99 (min)
oF
81
UOU
Mains Voltage calibration -30 ÷ 30 V 0