Ascon Tecnologic - K Series - ENGINEERING MANUAL - PAG. 30
]
AL1 Group (Alarm 1 Parameters)
no.
Para-
meter
Description Dec. Range Default
Vis.
Promo.
24 AL1t Alarm 1 type 0
nonE Alarm not used
LoAb Absolute low alarm
HiAb Absolute high alarm
LHAb Absolute band alarm
SE.br Sensor break
LodE Deviation low alarm (relative)
HidE Deviation high alarm (relative)
LHdE Relative band alarm
LoAb A-47
25 Ab1 Alarm 1 function 0
0... 15
+1 Not active at power ON
+2 Latched alarm (manual reset)
+4 Acknowledgeable alarm
+8 Relative alarm not active at set point change
0 C-0
26 AL1L
- For High and low alarms, it is the low
limit of the AL1 threshold
- For band alarm, it is low alarm threshold
dP From -1999 to AL1H ( E.U.) -1999 A-48
27 AL1H
- For High and low alarms, it is the high
limit of the AL1 threshold
- For band alarm, it is high alarm threshold
dP From AL1L to 9999 ( E.U.) 9999 A-49
28 AL1 AL1 threshold dP From AL1L to AL1H (E.U.) 0 A-50
29 HAL1 AL1 hysteresis dP 1... 9999 (E.U.) 1 A-51
30 AL1d AL1 delay dP From 0 (oFF) to 9999 (s) oFF C-0
31 AL1o Alarm 1 enabling during Stand-by mode 0
0 Never
1 During stand by
2 During overrange and underrange
3 During overrange, underrange and stand-by
no C-0
]
AL2 Group (Alarm 2 Parameters)
no.
Para-
meter
Description Dec. Range Default
Vis.
Promo.
32 AL2t Alarm 2 type 0
nonE Alarm not used
LoAb Absolute low alarm
HiAb Absolute high alarm
LHAb Absolute band alarm
SE.br Sensor break
LodE Deviation low alarm (relative)
HidE Deviation high alarm (relative)
LHdE Relative band alarm
HiAb A-54
33 Ab2 Alarm 2 function 0
0... 15
+1 Not active at power ON
+2 Latched alarm (manual reset)
+4 Acknowledgeable alarm
+8 Relative alarm not active at set point change
0 C-0
34 AL2L
- For High and low alarms, it is the low
limit of the AL2 threshold
- For band alarm, it is low alarm threshold
dP From -1999 to AL2H (E.U.) -1999 A-56
35 AL2H
- For High and low alarms, it is the high
limit of the AL2 threshold
- For band alarm, it is high alarm threshold
dP From AL2L to 9999 (E.U.) 9999 A-57
36 AL2 Alarm 2 threshold dP From AL2L to AL2H (E.U.) 0 A-58
37 HAL2 Alarm 2 hysteresis dP 1... 9999 (E.U.) 1 A-59
38 AL2d Alarm 2 delay dP From 0 (oFF) to 9999 (s) oFF C-0
39 AL2o Alarm 2 enabling during Stand-by mode 0
0 Never
1 During stand by
2 During overrange and underrange
3 During overrange, underrange and stand-by
no C-0