Ascon Tecnologic - K32 Line - ENGINEERING MANUAL - PAG. 4
2.5 Power Supply
Power Supply
14
13
Supply Voltage: •12VAC/DC(±10%);
•24VAC/DC(±10%);
•100...240VAC(±10%).
Current consumption: 5 W max.
Notes: 1. Before connecting the instrument to the power
line, make sure that line voltage is equal to the
voltage shown on the identification label;
2. To avoid electrical shock, connect power line at
the end of the wiring procedure;
3. For supply connections use No. 16 AWG or larger
wires rated for at last 75°C.
4. Use copper conductors only.
5. The polarity of the power supply has no importance;
6. The power supply input is NOT fuse protected.
Please, provide a T type 1A, 250 V fuse externally.
3. TECHNICAL CHARACTERISTICS
3.1 Technical specification
Case:
Plastic, self-extinguishing degree: V-0 according to UL 94;
Front protection: IP 65 (when the optional panel gasket is
mounted) for indoor locations according to EN 60070-1;
Terminals protection: IP 20 according to EN 60070-1;
Installation: Panel mounting;
Terminal block: 24 M3 screw terminals for cables of
0.25... 2.5 mm
2
(AWG22... AWG14) with connection diagram;
Dimensions: 78 x 33, depth 75.5 mm, (3.07 x 1.30 x 2.97 in.)
Panel cutout: 71(-0... +0.5) mm x 29(-0... +0.5)mm
2.80(-0... +0.023) x 1.14(-0... +0.023) in.];
Weight: 180 g max..
Power supply: • 12 VAC/DC (±10% of the nominal value);
• 24 VAC/DC (±10% of the nominal value);
•
100... 240 VAC (±10% of the nominal value);
Power consumption: 5 VA max.;
Insulation voltage: 2300 V rms according to EN 61010-1;
Display:
4 digit double display, red and green h: 7 mm;
Display updating time: 500 ms;
Sampling time: 130 ms;
Resolution: 30000 counts;
Total Accuracy: ±0.5% F.S.V. ±1 digit @ 25°C of room
temperature;
Electromagnetic compatibility and safety requirements
Compliance: Directive EMC 2004/108/CE (EN 61326-1),
directive LV 2006/95/CE (EN 61010-1);
Installation category: II;
Pollution category: 2;
Temperature drift: It is part of the global accuracy;
Operating temperature: 0... 50°C (32... 122°F);
Storage temperature: -30... +70°C (-22... +158°F);
Humidity: 20... 85% RH, not condensing;
Protections: WATCH DOG (hardware/software) for the
automatic restart.
4. HOW TO ORDER
Model
K32 (*) - = Controller
K32 (*) T = Controller+ timer
K32 (*) P = Controller + timer + programmer
Power supply
F = 12 VAC/DC
H = 100... 240 VAC
L = 24 VAC/DC
Analogue input + 2 Digital Inputs (always present)
C = J, K, R, S, T, PT100, 0/12...60 mV
E = J, K, R, S, T, PTC, NTC, 0/12...60mV
I = 0/4... 20 mA
V = 0... 1V, 0/1... 5V, 0/2... 10V
Output 1
R = Relay SPDT 8 A (resistive load)
O = VDC for SSR
Output 3
- = Not available
R = Relay SPST 5 A (resistive load)
O = VDC for SSR
Output 4
- = Not available
R = Relay SPST 5 A (resistive load)
O = VDC for SSR
Serial Communications
- = TTL Modbus
S = RS485 Modbus
Output 2
- = Not available
R = Relay SPDT 8 A (resistive load)
O = VDC for SSR
- -
Packaging
- = “Butterfly” type brackets (standard)
V = Screw type bracket
-
= Reserved Codes
(*) Please add the letter S if you want the “Sensitive
Touch” keyboard. (capacitive type keyboard).