Ascon Tecnologic - K Series - ENGINEERING MANUAL - Vr. 9.0 PAG. 20
[117] diSP - Secondary Display management
Available: Always.
Range: nonE = Standard display;
Pou = Power output;
SPF = Final set point;
Spo = Operative set point;
AL1 = Alarm 1 threshold;
AL2 = Alarm 2 threshold;
AL3 = Alarm 3 threshold;
Pr.tu = - During a soak, the instrument shows the
elapsed time of the soak.
- During a ramp the display shows the ope-
rative set point.
At the end of program execution, the
instrument shows P.End messages alter-
nated with the measured value.
- When no program is running, the instru-
ment shows the standard display.
Pr.td =
- During a soak, the instrument shows the
remaining time of the soak (count down).
- During a ramp the display shows the ope-
rative set point.
At the end of program execution, the
instrument shows P.End messages alter-
nated with the measured value.
- When no program is running, the instru-
ment shows the standard display.
P.t.tu = When the programmer is running, the di-
splay shows the total elapsed time. At the
end of the program execution, the instru-
ment shows p.End messages alternated
with the measured value.
P.t.td =
When the programmer is running, the display
shows the total remaining time (count down).
At the end of the program execution, the
instrument shows p.End messages alter-
nated with the measured value.
ti.uP =
When the timer is running, the display shows
the timer counting up. At the end of the
counting, the instrument shows t.End mes-
sages alternately with the measured value.
ti.du =
When the timer is running, the display shows
the timer counting down. At the end of the
counting, the instrument shows t.End mes-
sages alternately with the measured value.
PErc =
Percent of the power output used during soft
start (when the soft start time is equal to in-
finite, the limit is always active and it can be
used also when ON/OFF control is selected).
[119] FiLd - Filter on the displayed value
Available: Always.
Range: oFF = Filter disabled
0.1... 20.0 in engineering units.
Note: This is a “window filter” related to the set point; it is ap-
plied to the displayed value only and has no effect on the
other instrument functions (control, alarms, etc.).
[120] dSPu - Instrument Status at Power ON
Available: Always.
Range: AS.Pr = Starts in the same way it was prior to the
power down;
Auto = Starts in Auto mode;
oP.0 = Starts in manual mode with a power output
equal to zero;
St.bY = Starts in stand-by mode.
[121] oPr.E - Operative modes enabling
Available: Always.
Range: ALL = All modes will be selectable by the next
parameter;
Au.oP = Auto and manual (oPLo) mode only will be
selectable by the next parameter;
Au.Sb = Auto and Stand by modes only will be se-
lectable by the next parameter.
Notes: 1. When you change the value of [121] oPr.E, the
instrument forces [122] oPEr parameter to Auto.
2. During program execution the instrument stores
the segment currently in use and, by a 30 minutes
interval, stores also the elapsed time of the soaks.
If a power down occurs during program execu-
tion, at the next Power ON the instrument is able
to continue the program execution starting from
the segment in progress at power down and, if the
segment was a soak, it is also capable to restart
from the soak time minus the stored elapsed time
(with an approximation of 30 minutes).
In order to obtain this features, the [120] dSPu -
Status of the instrument at Power ON parameter
must be set to AS.Pr.
If the [120] dSPu is different than AS.Pr
the
memorization function will be hinibit.
[122] oPEr - Operative mode selection
Available: Always.
Range: • When [121] oPr.E = ALL:
Auto = Auto mode;
oPLo = Manual mode;
St.bY = Stand by mode.
• When [121] oPr.E = Au.oP:
Auto = Auto mode;
oPLo = Manual mode;
• When [121] oPr.E = Au.Sb:
Auto = Auto mode;
St.bY = Stand by mode.
]Ser Group - Serial link parameters
[123] Add - Instrument address
Available: Always.
Range: oFF = Serial interface not used;
1... 254 Instrument address.
[124] bAud - Baud rate
Available: When [123] Add different from oFF.
Range: 1200 = 1200 baud;
2400 = 2400 baud;
9600 = 9600 baud;
19.2 = 19200 baud;
38.4 = 38400 baud.
[125] trSP - Selection of the value to be
retransmitted (Master)
Available: When [123] Add is different from oFF.
Range: nonE = Retransmission not used (the instrument is
a slave);
rSP = The instrument becomes a Master and
retransmits the operative set point;
PErc = The instrument becomes a Master and
retransmits the power output.
Note: For more details see [80] SP.rt (Remote set point type)
parameter.