AC112Q-3, AC125Q-3, AC150Q-3, and AC165Q-3 Operations Manual.... 46
TRANSFER ON OVERLOAD CONTROL
Feature: Disabled, Select Genset: 1
Enable Disable Forward Back Exit
7.3 LOAD MANAGEMENT OPERATION, cont.
7.3.4 Automatic Transfer to Generator, Single or Master Converters (Seamless Transfer
installed)
Upon Shore Alarm, the Automatic Transfer to Generator feature may be used to perform a
Seamless Transfer to a pre-selected generator. This implies connection and setting of the Generator
Autostart Control feature (needed to signal a generator to start and hold the set warm-up time
before transferring). The transfer is not initiated until Voltage Droop has occurred as the load
savings afforded may have taken the converter out of Shore Cord Alarm.
From the front panel, press the SHORE POWER + F2 buttons, and then Transfer (F3) to access
the following screen:
Press the F1 or F2 buttons to adjust the Feature or Select Genset settings; Forward (F3) to advance
the cursor to the Select Genset setting; Back (F4) to return the cursor to the Feature setting, and
Exit (F5) to save the settings and exit the screen. When the cursor is on the Feature setting, the
F1/F2 buttons will read Enable/Disable. When the cursor is on the Select Genset setting, the
F1/F2 buttons will read More/Less.
Default Range
Feature DISABLED DISABLED/ENABLED
Genset 1 - 4