AC112Q-3, AC125Q-3, AC150Q-3, and AC165Q-3 Operations Manual.... 47
7.3 LOAD MANAGEMENT OPERATION, cont.
7.3.5 Quick Setup of Shore Cord Alarm, Single, Master, or Slave Converters
1. Turn on the red Disconnect switch of both converters and wait 15-20 seconds for initialization.
2. Press the SHORE POWER + F2 buttons on both converters.
3. Press the Cursor (F4) button to advance to the ALARM AT % setting.
4. Set the converter ALARM AT % using the More/Less (F1/F2) buttons.
5. Press the Cursor (F4) button to advance to the ALARM enable setting.
6. Set the converter ALARM enable using the Enable/Disable (F1/F2) buttons.
7. Press the Exit (F5) button to save the settings and exit.
8. Turn on the converters and place online as usual. Alarm will occur when loading reaches the
ALARM AT % setting.
Quick Setup of Load Sharing, paralleled Converters
1. Turn on the red Disconnect switch of both converters and wait 15-20 seconds for initialization.
2. Press the SHORE POWER + F2 buttons on both converters.
3. Press CORD (F1) on both converters.
4. Set the Master’s SHORE CORD AMPACITY in amps using the More/Less (F1/F2) buttons.
5. Set the Slave’s MASTER CAPACITY in kVA (read from the Master’s Shore Cord Setup
screen) using the More/Less (F1/F2) buttons.
6. Advance to the Slave’s SLAVE CORD AMPACITY using the Forward (F3) button and set the
amps using the More/Less (F1/F2) buttons.
7. Press the Exit (F5) button twice on both converters to save the settings and exit.
8. Turn on the converters and place online as usual, and verify an imbalanced share in Load Level
% or individual Converter Output Amps at a ratio approximate to that ratio between the converter’s
programmed capacities.