20
This calculation is intended as a guide only and no warranty is made or implied by Astral Pool as to its
accuracy. Please consult an Acoustical Consultant or phone your Astral Pool branch office if in any
doubt.
Further Guidelines for installation of Heat Pumps
ASTRAL POOL Heat Pumps must be installed outdoors – never install inside a plant room,
garage etc.
Allow a minimum of 500mm clearance from the sides and rear of the heat pump and a minimum
of 1000mm service access from the front of the Heat Pump.
Ensure an electrical isolation switch is located nearby the Heat Pump.
On Three Phase models, ensure the phase rotation of the compressor is checked before
commissioning of the unit.
Ensure the water pressure switch operation is checked at least 6 times prior to handing over the
Heat Pump.
Refer to Installation and Operating Instructions for full installation, commissioning and operating
procedures.