Flue gas system
Connections
Collective flue gas outlet overpressure
Diameter and venting lengths of the flue gas outlet/air supply:
Closed system with over-pressure.
Closed system, overpressure, parallel
Output (80/60) d = minimum diameter Ø in mm
[kW] h = 2 - 5 h = 6 - 10 h = 11 - 15 h = 16 - 20
114 285 150 150 150 150
285 - 524 150 200 200 200
524 - 1440 180 300 300 300