Technical description
Sales text ATAG XL-W 105
ATAG XL-W 105
Wall-hung condensing gas boiler
Overview of features:
compact, pre-assembled construction and ready for connection
stainless steel heat exchanger
Insulation in expanded polypropylene
premixed burner in material ceramic for continuous adjustment of power
Control unit ACP for combustion management, modulation and safety pump modulation management and
flow measurement via the ACP unit
combustion control with the ionization principle
automatic temperature control
0-10 V DC input for connection to an external regulation system
alarm output or operating status
connections for the flow probe of the heating circuit, DHW and external probe
ACP control unit with LCD display capacitive touch with led indication status: active / standby / lock, oper-
ating mode selection DHW or central heating, cascade manager integrated, chimney sweep mode with
power selection minimum / maximum regardless of outside temperature, regulation of the heating flow tem-
perature, DHW temperature regulation, e-bus2 connections for connection with accessories from the ATAG
offer
Ready for connection to BMS systems supported protocols Modbus, bacnet, lonworks, KNX with dedicated
accessory
Ready for systems management, solar thermal through dedicated accessory
Possibility of pump management DHW circuit via diverter valve or storage heating pump, single heating
zone management via power supply pump and modulation
Operating hours counter, alarm and fault history
support for wall mounting included
automatic air vent valve
flue non return valve
modulating pump pre-mounted in the boiler modulating with flow measurement and diagnostics
Nominal thermal power at full load
with 80/60°C: 89.4 kW
with 50/30°C: 99.0 kW
Nominal heat input full load Net: 92.3 kW
Gross seasonal efficiency: 95,.2%
Type of gas: natural gas
Gas inlet pressure max/min: 25-17mbar
NOx: < 24 mg/kWh
BREEAM credits: 2
Electrical connection: 230 V (50 Hz)
Dimensions (HxWxD): 1050x530x675 mm
Weight: 80 kg
Fittings
- air / flue gas: 100/100 mm
- water: R 2 ''
- gas: R 1/2 ''
Efficiency class: A / A
SSIGA approval:
For water quality information refer to the instruction booklet