Rectification of Faults
Fault Possible cause Rectification
The water level in the primary
settling stage is unusually high,
whereby a normal water level is
present in the aeration stage.
The charging pipeline is
leaking and draws in air.
Check the screw
connection for tightness. If
a hose is available as
charging line the securing
of the hose and the leak
tightness of the hose should
be checked.
The charging pipeline is
blocked.
The water transmissibility
can be checked in manual
operation.
The submersible motor
pump is defective.
Call the Service.
There is air in the impeller
chamber of the pump. This
condition can be detected
through a gurgling sound.
The bleeding of this
chamber is ensured through
a small drilling in the lower
third of the pump casing.
Remove AQUAmax
®
and
check the drilling, if
required, clean.
The water level in the primary
settling stage and in the
aeration stage is unusually
high. The control system
indicates “Flooding alarm”.
Unusually high infiltration
water inflow. With heavy
rainfall due to surface water
or rain-sodden ground due
to leaking concrete tank.
Infiltration water may not
ingress into the wastewater
treatment plant over a
longer period. If necessary,
seal concrete tank or
remedy other causes.
The submersible motor
pump is blocked or
defective.
Check the pump with
manual operation, if
required, call Service.
There is a back-up at the
discharge point. The water
conveyed by the pump flows
back again.
The discharge point must be
made free again.
The water level in the primary
settling stage and in the
aeration stage is unusually
high. The control system
indicates “Energy-saving
operation”.
The float switch cannot float
up because it is limited its
freedom of movement.
Check the float switch (see
Manual Mode).ÆDoes not
apply for BASIC.
The float switch is defective
or the cable is interrupted.
Call Service.
The water levels in the primary
settling stage and in the
aeration stage are always the
same, although water flows into
the primary settling stage.
The partition wall between
aeration stage and primary
settling stage is not
watertight.
Close partition wall slits and,
if necessary, reseal partition
wall joints.
The hydraulic system in the
AQUAmax
®
for the
interruption of the charging
pipeline is impaired.
Call Service.