SMART TDS & BOTTOM BLOWDOWN CONTROLLER
5.2.11 Password
This function is used to change the password of the device.
Press button to enter to function menu.
and buttons increase or decrease digits and
button shift right to the next digit.
After change the last digit, button accepts the new
password.
It is important that if the default pass code is changed that the new value is noted
and kept safe.
Default password 000
New password
5.2.12 Default Settings
If the default settings are needed, "Default Settings" function could be selected from
the menu.
To select "Default Settings", press button for 5 second on this function.
After confirming "Ok" on the screen, will be returned to the
menu. Default settings as below :
Conductivity Set Point : 5.000 uS/cm
Conductivity Hysteresis : 300 uS/cm
Conductivity Alarm : 9.500 uS/cm
Alarm Hysteresis : 300 uS/cm
Conductivity Blowdown System On/Off : System On
Bottom Blowdown Interval : 8 h
Bottom Blowdown Time/Duration : 5 sn
Bottom Blowdown System On/Off : System On
IM-BC970-18F Page 13
BC 970
www.atech-ltd.com