13/08/2013 PM 9845 0187 01 Page 20 of 24
11.5.3. Change the active pressure band
Please refer to the Address Mapping document, created by Speci5, to get the correct Register and Value for adjusting the
Pressure Band Selection.
In this case f.i. the correct Register is 16#03 16#5C. To switch from Pressure Band 1 to Pressure Band 2, value 16#00
16#02 will have to be used.
NOTE: Make sure that Pressure Band 1 is used before actually sending the request.
Request : 16#05 16#06 16#03 16#5C 16#00 16#02 16#C9 16#D9
Answer : 16#05 16#06 16#03 16#5C 16#00 16#02 16#C9 16#D9
11.5.4. Start the machine
Please refer to the Address Mapping document, created by Speci5, to get the correct Register and Value to start the
machine.
In this case f.i. the correct register is 16#07 16#D0 and the correct value is 16#00 16#01.
NOTE: Make sure the machine is in LAN Control before actually sending the request.
Request : 16#05 16#06 16#07 16#D0 16#00 16#01 16#49 16#03
Answer : 16#05 16#06 16#07 16#D0 16#00 16#01 16#49 16#03