QAS28 Yd(S), QAS28 YdS IT
16
'
85,1*
23(5$7,21
Following points should be carried out regularly:
– Check the engine gauges and the lamps for normal readings.
– Check for leakage of oil, fuel or cooling water.
– Avoid long low-load periods (< 30 %). In this case, an output drop
and higher oil consumption of the engine could occur.
– Check, by means of the generator gauges, that the voltage between
the phases is identical and that the rated current per phase is not ex-
ceeded.
– When single-phase loads are connected to the generator output ter-
minals, keep all loads well-balanced.
If circuit breakers are activated during operation, switch off the
load and stop the generator. Check and, if necessary, decrease the
load.
The generator’s side doors may only remain opened for short peri-
ods during operation, to carry out checks for example.
6
7233,1*
– Switch off the load.
– Switch off circuit breakers.
– Let the engine run for about 5 minutes.
– Stop the engine by putting the starter switch in position O.
– Lock the side doors and the door of the indicators and control panel
to avoid unauthorized access.
Avoid to let the engine run out of fuel. If it hap-
pened, priming will speed up the starting.