Page #54 background imageLoading...
Page #54 background image
Status indication S0007 displays a fault.The fault Thermoswitch is displayed
when selecting Details.
The motor has to cool down before the operation can be resumed. Depending on
the parameter setting, the fault signal is either automatically reset or the fault signal
has to be reset using the push button Reset in selector switch position LOCAL.
For further information to this topic, please refer to Manual (Operation and setting).
54
SQ 05.2 SQ 14.2/SQR 05.2 SQR 14.2 Control unit: electronic (MWG)
Corrective action AC 01.2 Non-Intrusive