Upper Bound of Output Frequency Mem Addr 060FH(41552)
Range: 0.1 to 400 Hz Default Setting: 400.0
This parameter must be equal to or greater than the Lower Bound of Output
Frequency (6-16).
Lower Bound of Output Frequency Mem Addr 0610H(41553)
Range: 0.0 to 400 Hz Default Setting: 0.0
This parameter must be less than or equal to the Upper Bound of Output
Frequency (6-15).
The Upper/Lower Bound is to prevent operation error and machine damage.
• If the Upper Bound of Output Frequency is 50 Hz and the Maximum Output
Frequency is 60 Hz, the Maximum Output Frequency will be limited to 50 Hz.
• If the Lower Bound of Output Frequency is 10 Hz, and the Minimum Output
Frequency (2-06) is set at 1.0 Hz, then any Command Frequency between 1-10 Hz
will generate a 10 Hz output from the drive.
6-16
6-15
GS1 Series AC Drive User Manual
4–43
Chapter 4: AC Drive Parameters
Input frequency
Output frequency
6-15
6-16