EasyManuals Logo

Automationdirect.com GS1-21P0 User Manual

Default Icon
137 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #73 background imageLoading...
Page #73 background image
Chapter 4: AC Drive Parameters
GS1 Series AC Drive User Manual
4–34
Example 3: Forward and Reverse Operation
In this example, the potentiometer is programmed to run a motor full-speed in
both forward and reverse direction. The frequency reference will be 0Hz when the
potentiometer is positioned at mid-point of its scale. Parameter 4-04 must be set to
enable reverse motion.
Note: When calculating the values for the Analog Input using reverse motion, the
reverse frequency reference should be shown using a negative (-) number. Pay special
attention to signs (+/-) for values representing reverse motion.
• Minimum Frequency Reference = -60Hz (reverse)
• Maximum Frequency Reference = 60Hz
Calculations
A)
B)
Note: The negative (-) value for the Analog Offset % shows that a negative offset is
needed for 4-01.
C)
D)
Parameter Settings
4-01: 2 – Negative Input Offset Polarity
4-02: 100 – 100% Analog Input Offset
4-03: 200 – 200% Analog Input Gain
4-04: 1 – Reverse Motion Enable
Results
Mid-point Frequency =
2
60Hz – (-60Hz)
()
+ (-60Hz) = 0Hz
Analog Gain % =
60Hz
60Hz – (-60Hz)
( )
x 100 = 200%
Analog Offset % =
-60Hz
60Hz
()
x 100 = -100%
x 60Hz = 60Hz
Max. Output Frequency =
1750 RPM
1750 RPM
( )
-60 60Hz
0
Potentiometer Scale
0V
10V
4mA
20mA
60Hz
20mA
10V
-60Hz
0V
4mA
Maximum Output
Frequency
5V
12mA
0Hz
Forward
Reverse

Questions and Answers: