EasyManuals Logo

Automationdirect.com GS1-21P0 User Manual

Default Icon
137 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #80 background imageLoading...
Page #80 background image
GS1 Series AC Drive User Manual
4–41
Chapter 4: AC Drive Parameters
Over-current Stall Prevention during Acceleration Mem Addr 060AH(41547)
Range: 20 to 200% Default setting: 150
A setting of 100% is equal to the Rated Output Current of the drive.
• Under certain conditions, the AC drive output current may increase abruptly,
and exceed the value specified by 6-10 This is commonly caused by rapid
acceleration or excessive load on the motor. When this function is enabled, the
AC drive will stop accelerating and maintain a constant output frequency. The
AC drive will only resume acceleration when the current drops below the
maximum value.
Over-current Stall Prevention during Operation Mem Addr: 060BH(41548)
Range: 20 to 200% Default Setting: 150
• During steady-state operation with motor load rapidly increasing, the AC drive
output current may exceed the limit specified in 6-11. When this occurs, the
output frequency will decrease to maintain a constant motor speed. The drive
will accelerate to the steady-state output frequency only when the output
current drops below the level specified by 6-11.
6-11
6-10
Output current
Over-current
detection
level
Output current
tim e
Output
frequency
output
freq
tim e
Over-current Stall Prevention
during Operation
tim e
6-10
tim e
Over-current
detection
level
6-11
Over-current Stall Prevention
during Acceleration

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Automationdirect.com GS1-21P0 and is the answer not in the manual?

Automationdirect.com GS1-21P0 Specifications

General IconGeneral
BrandAutomationdirect.com
ModelGS1-21P0
CategoryController
LanguageEnglish

Related product manuals