Built–in I/O Specifications – Outputs
Outputs per Module
6
Operating Voltage Range
6–240 VAC (47–63 Hz), 6–27 VDC
Output Voltage Range
5–264 VAC (47–63 Hz), 5–30 VDC
Output Type
Relay, form A (SPST)
Maximum Current
1 A/point;
C3: 4A/common, C4: 2A/common
Minimum Load Current
5mA @ 5VDC
Maximum Inrush Current
3A for 10ms
OFF to ON Response
< 15ms
ON to OFF Response
< 15ms
Status Indicators
Logic Side (6 points, red LED)
Commons
2 (4 points/com &
2 points/com) Isolated
Typical Relay Life (Operations)
at Room Temperature
Voltage & Load Type Relay Life
30VDC, 1A Resistive 300,000 cycles
30VDC, 1A Solenoid 50,000 cycles
250VAC, 1A Resistive 500,000 cycles
250VAC, 1A Solenoid 200,000 cycles
ON to OFF = 1 cycle
C0-10ARE-D – 8 AC Input/6 Relay Output Micro PLC (continued)
OUTPUT
Y1-Y4
Typical
COM
6-27 VDC
L
Internal Module Circuitry
Equivalent Output Circuit
6-240 VAC
C3
OUTPUT
Y5-Y6
Typical
COM
6-27 VDC
L
6-240 VAC
C4
To Y2-Y4
commons
To Y6
common
ZIPLink Pre-Wired PLC Connection
Cables and Modules for CLICK PLC
ZL-RTB20
20-pin feed-through
connector module
20-pin connector cable
ZL-C0-CBL20 (0.5 m length)
ZL-C0-CBL20-1 (1.0 m length)
ZL-C0-CBL20-2 (2.0 m length)
55 °C
131 °F
0
Surrounding Air Te mperature C/°F)
32
10
50
20
68
30
85
40
104
50
122
2
4
6
8
Points
C0-10ARE-D Temperature Derating Chart
0
45
113
Outputs
* Use every other output.
*
CLICK PLC Hardware User Manual, 6th Edition, Rev. G – C0-USER-M
2–67
Chapter 2: Specifications