Built-in I/O Specifications - Inputs
Inputs per Module
8
Operating Voltage Range
100–120 VAC
Input Voltage Range
80–144 VAC
AC Frequency
47–63 Hz
Input Current
8.5 mA @ 100VAC at 50Hz
10 mA @ 100VAC at 60Hz
Maximum Input Current
16 mA @ 144VAC
Input Impedance
15kq @ 50Hz
12kq @ 60Hz
ON Voltage Level
> 60VAC
OFF Voltage Level
< 20VAC
Minimum ON Current
5mA
Maximum OFF Current
2mA
OFF to ON Response
Max 40ms
ON to OFF Response
Max 40ms
Status Indicators
Logic Side (8 points, green LED)
Commons
2 (4 points/common) Isolated
General Specifications
Current Consumption at 24VDC
140mA
Terminal Block Replacement Part No.
C0-16TB
Weight
5.6 oz (160g)
C0-01AR-D – 8 AC Input/6 Relay Output Micro PLC
RS-485
PORT3
PORT2
PORT1
PWR
RUN
ERR
TX2
RX2
TX1
RX1
TX3
RX3
R
S-485
P
ORT3
PO
RT
2
PO
RT
1
PWR
RUN
ERR
TX
2
R
X
2
TX1
RX1
TX
3
RX3
100 - 120VAC
6 - 240VAC
L
6-27VDC
L
L
L
L
L
6 - 240VAC
6-27VDC
C0-01AR-D
C1
X1
X2
X3
X4
C2
X5
X6
X7
X8
C3
Y1
Y2
Y3
Y4
C4
Y5
Y6
0
Surrounding Air Temperature C/°F)
32
10
50
20
68
30
85
40
104
50
122
55 °C
131 °F
2
4
6
8
Points
C0-01AR-D Temperature Derating Chart
0
Inputs
INPUT
COM
100-120 VAC
Internal Module Circuitry
Optical Isolator
Equivalent Input Circuit
INPUT
COM
100-120 VAC
Optical Isolator
X1-X4
Typical
X5-X8
Typical
C1
C2
To X6-X8
commons
To X2-X4
commons
Wiring Diagram
NOTE: When using Standard PLCs, you
must use CLICK programming software
version V1.20 or later.
CLICK PLC Hardware User Manual, 6th Edition, Rev. G – C0-USER-M
2–49
Chapter 2: Specifications

Table of Contents