Output Specifications
Outputs per Module
8
Operating Voltage Range
17–240 VAC
Output Voltage Range
13.5–288 VAC
AC Frequency
47–63 Hz
Maximum Output Current
0.3 A/point, 1.2 A/common
Minimum Load
10mA
Maximum Leakage Current
4mA @ 288 VAC
On Voltage Drop
1.5 VAC @ > 0.1 A
3.0 VAC @ < 0.1 A
Maximum Inrush Current
10A for 10ms
OFF to ON Response
1ms
ON to OFF Response
1ms + 1/2 cycle
Status Indicators
Logic Side (8 points, red LED)
Power Indicator (green LED)
Commons
2 (4 points/common) Isolated
Bus Power Required (24VDC)
Max. 80mA (All Outputs On)
Protection Circuit
Not built into the module - Install protection
elements such as external fuse.
Terminal Block Replacement
AutomationDirect p/n C0-8TB
Weight
3.5 oz (100g)
C0-08TA – 8-Point AC Output Module
8-point 17-240 VAC triac output module, 2 commons, isolated, 0.3 A/pt, removable terminal
block included.
0
Surrounding Air Te mperature C/°F)
32
10
50
20
68
30
85
40
104
50
122
55 °C
131 °F
2
4
6
8
Points
Output Temperature Derating Chart
0
0.2 A/pt.
0.3 A/pt.
*
* Use every other output.
OUTPUT
COM
17-240 VAC
L
Internal Module Circuitry
Optical Isolator
Equivalent Output Circuit
* Varistor Joule Rating: 20 J
*
C0-08TA
17-240V 0.3A
50-60Hz
PWR
OUTPUT
C0
-
08TA
17-2
40V
0.3A
50-60H
z
P
WR
V
V
O
UTP
UT
17 - 240VAC
L
L
L
L
17 - 240VAC
N.C.
N.C. = Not Connected
L
L
L
L
C2
7
3
2
5
4
8
6
1
C1
ZIPLink Pre-Wired PLC Connection
Cables and Modules for CLICK PLC
11-pin connector cable
ZL-C0-CBL11 (0.5 m length)
ZL-C0-CBL11-1 (1.0 m length)
ZL-C0-CBL11-2 (2.0 m length)
Wiring Diagram
ZL-RTB20
20-pin feed-through
connector module
CLICK PLC Hardware User Manual, 6th Edition, Rev. G – C0-USER-M
2–125