General Specifications
Field to Logic Side Isolation
1800VAC for 1 sec.
External 24VDC Power
Required
65mA
Base Power Required (24VDC)
20mA
Terminal Block Replacement
AutomationDirect p/n
C0-16TB
Weight
3.1 oz (86g)
Input Specifications
Inputs per Module
4
Input Range
0–10 V
Resolution
13-bit, 1.22 mV per count
Input Type
Single ended (one common)
Maximum Continuous Overload
±100VDC
Input Impedance
>150kΩ
Filter Characteristics
Low pass, -3dB at 500Hz
Sample Duration Time
5ms
All Channel Update Rate
20ms
Open Circuit Detection Time
Zero reading within 100ms
Conversion Method
Successive approximation
Accuracy vs. Temperature
±75 PPM/°C maximum
Maximum Inaccuracy
0.5% of range (including
temperature changes)
Linearity Error (End to End)
±3 count maximum,
monotonic with no missing
codes
Input Stability and Repeatability
±2 count maximum
Full Scale Calibration Error
(including Offset)
±8 count maximum
Offset Calibration Error
±8 count maximum
Maximum Crosstalk at DC,
50/60 Hz
±2 count maximum
C0-4AD2DA-2 – 4-Channel Analog Voltage Input and 2-Channel Analog
Voltage Output Module
4-channel analog voltage input (13-bit resolution) and 2-channel analog voltage output (12-bit
resolution) module, range: 0-10V. External 24VDC power required, removable terminal block
included.
C0-4AD2DA-2
0-10V
OUTPUT
INPUT
CH1
0V
CH2
0V
CH3
0V
CH4
0V
CH1
0V
CH2
0V
24V
0V
All ‘0V’
terminals are
connected
internally.
C0
-4AD2DA-
2
0
-
10V
OUTPUT
I
NPUT
C
H1
0V
C
H2
0V
C
H
3
0V
C
H4
0V
C
H1
0
V
C
H2
0V
2
4
V
0V
Al
l
te
r
co
i
n
t
N.C.
N.C.
N.C.
N.C.
N.C.
N.C.
24VDC
Power
Supply
Ch1
Load
Ch2
Load
+
Voltage
Transmitter
+
Voltage
Transmitter
+
+
Voltage
Transmitter
Voltage
Transmitter
+
CHn
0V
Connect the unused input
channel to 0V terminal.
N.C. = Not Connected
ZIPLink Pre-Wired PLC Connection
Cables and Modules for CLICK PLC
20-pin connector cable
ZL-C0-CBL20 (0.5 m length)
ZL-C0-CBL20-1 (1.0 m length)
ZL-C0-CBL20-2 (2.0 m length)
ZL-RTB20 20-pin feed-
through connector module
Wiring Diagram
NOTE: When using this module you must
also use CLICK programming software and
PLC firmware version V1.40 or later.
CLICK PLC Hardware User Manual, 6th Edition, Rev. G – C0-USER-M
2–146
Chapter 2: Specifications

Table of Contents

Related product manuals