C0-00DD2-D – 8 DC Input/6 Sourcing DC Output Micro PLC (continued)
OUTPUT Y5-Y6
24 VDC
L
Internal Module Circuitry
Optical Isolator
+
Equivalent Output Circuit
V2
OUTPUT Y1
24 VDC
L
Optical Isolator
+
V1
Y1
High response
circuit
OUTPUT Y2-Y4
L
Optical Isolator
COMCO
*
*
*
*Zener Diode Power Dissipation: 200 mW
ZIPLink Pre-Wired PLC Connection
Cables and Modules for CLICK PLC
20-pin connector cable
ZL-C0-CBL20 (0.5 m length)
ZL-C0-CBL20-1 (1.0 m length)
ZL-C0-CBL20-2 (2.0 m length)
0
Surrounding Air Temperature C/°F)
32
10
50
20
68
30
85
40
104
50
122
55 °C
131
°F
2
4
6
8
Points
C0-00DD2-D Temperature Derating Chart
0
Outputs
ZL-RTB20
20-pin feed-through
connector module
Built-in I/O Specifications - Outputs
Outputs per Module
6 (Source)
Operating Voltage Range
24VDC
Output Voltage Range
19.2–30 VDC
Maximum Output Current
0.1 A/point , 0.6 A/common
Minimum Output Current
0.2 mA
Maximum Leakage Current
0.1 mA @ 30VDC
On Voltage Drop
Y1: 1.0 VDC @ 0.1 A
Y2-6: 0.5 VDC @ 0.1 A
Maximum Inrush Current
150mA for 10ms
OFF to ON Response
Y1: typ 5μs; max 20μs
Y2-6: < 0.5 ms
ON to OFF Response
Y1: typ 5μs; max 20μs
Y2-6: < 0.5 ms
Status Indicators
Logic Side (6 points, red LED)
Commons
1 (6 points/common)
CLICK PLC Hardware User Manual, 6th Edition, Rev. G – C0-USER-M
2–38
Chapter 2: Specifications

Table of Contents