Chapter 4: AC Drive Parameters
4–72
Display Parameters
User Defined Display Function
Default Setting: 00
Settings:
00 Output Frequency (Hz)
01 Motor Speed (rpm)
02 Scaled Frequency
03 Output Current (A)
04 Motor Load (%)
05 Output Voltage (V)
06 DC Bus Voltage (V)
07 PID Setpoint
08 PID Feedback (PV)
09 Frequency Setpoint
Frequency Scale Factor
Default Setting: 1.0
Range: 0.01 to 160.0
This parameter can be used to multiply the display unit by a scaling factor so that
the display will represent some other user desired unit. For example, the user may
want to scale the drive display to represent ft/min for a motor that is driving a
conveyor.
The coefficient K determines the multiplying factor for the user-defined unit.
• The display value is calculated as follows:
Display value = output frequency x K
• The display window is only capable of showing four digits, but P8.01 can be used
to create larger numbers. The display window uses decimal points to signify
numbers up to five digits as explained below:
DISPLAY NUMBER REPRESENTED
9999 The absence of a decimal point indicates a four digit integer.
999.9 A single decimal point between the middle and the right-most numbers
is a true decimal point; it separates ones and tenths as in “300.5 (three
hundred and one-half).
9999. A single decimal point after the right-most number is not a true
decimal point; instead it indicates that a zero follows the right-most
numbers. For example, the number 12340 would be displayed as
“1234.”.
Backlight Timer
Default Setting: 00
Settings:
00 Timer Enable (1 min light off)
01 Timer Disable
This parameter is used to enable or disable the backlight timer.
P8.02
P8.01
P8.00
DURAPULSE AC Drive User Manual
1st Ed. Rev. D 05/2013