Chapter 5: DURAPULSE MODBUS Communications
5–2
Communications Parameters Summary
A summary of the DURAPULSE Communications Parameters is listed below. For a
complete listing of the DURA
PULSE Parameters, refer to CHAPTER 4.
Communications Parameters Summary
Parameter Description Range Default
P9.00
Communication Address 01 to 254 01
P9.01
Transmission Speed
00: 4800 baud
01: 9600 baud
02: 19200 baud
03: 38400 baud
01
P9.02
Communication Protocol
00: MODBUS ASCII mode
7 data bits, no parity, 2 stop bits
01: MODBUS ASCII mode
7 data bits, even parity, 1 stop bit
02: MODBUS ASCII mode
7 data bits, odd parity, 1 stop bit
03: MODBUS RTU mode
8 data bits, no parity, 2 stop bits
04: MODBUS RTU mode
8 data bits, even parity, 1 stop bit
05: MODBUS RTU mode
8 data bits, odd parity, 1 stop bit
00
P9.03
Transmission Fault Treatment
00: Display fault and continue operating
01: Display fault and RAMP to stop
02: Display fault and COAST to stop
03: No fault displayed and continue operating
00
P9.04
Time Out Detection
00: Disable
01: Enable
00
P9.05
Time Out Duration 0.1 to 60.0 seconds 0.5
P9.07
Parameter Lock
00: All parameters can be read and set
01: All parameters are read-only
00
P9.08
Restore to Default 99: Restores all parameters to factory defaults 00
P9.11
Block Transfer Parameter 1 P0.00 to P8.02, P9.99 P9.99
P9.12
Block Transfer Parameter 2 P0.00 to P8.02, P9.99 P9.99
P9.13
Block Transfer Parameter 3 P0.00 to P8.02, P9.99 P9.99
P9.14
Block Transfer Parameter 4 P0.00 to P8.02, P9.99 P9.99
P9.15
Block Transfer Parameter 5 P0.00 to P8.02, P9.99 P9.99
P9.16
Block Transfer Parameter 6 P0.00 to P8.02, P9.99 P9.99
P9.17
Block Transfer Parameter 7 P0.00 to P8.02, P9.99 P9.99
P9.18
Block Transfer Parameter 8 P0.00 to P8.02, P9.99 P9.99
P9.19
Block Transfer Parameter 9 P0.00 to P8.02, P9.99 P9.99
P9.20
Block Transfer Parameter 10 P0.00 to P8.02, P9.99 P9.99
P9.21
Block Transfer Parameter 11 P0.00 to P8.02, P9.99 P9.99
P9.22
Block Transfer Parameter 12 P0.00 to P8.02, P9.99 P9.99
P9.23
Block Transfer Parameter 13 P0.00 to P8.02, P9.99 P9.99
Parameter can be set during RUN Mode.
DURAPULSE AC Drive User Manual
1st Ed. Rev. D 05/2013