3–17
Write Parameter Settings to Keypad
After P9.40 COPY KEYPAD is enabled, the LCD display will show an additional
group called COPY KEYPD GROUP. Press the PROGRAM key and then the
UP/DOWN or PROGRAM keys until this new group is displayed.
Press the ENTER key to display the copy mode selections.
Select the WRITE TO KEYPAD mode using the UP/DOWN keys.
Press the ENTER key to display the four (4) available program numbers to write
from the AC drive to the keypad. The program name will automatically be named
the part number of the AC drive, for example: GS3-22P0.
Use the UP/DOWN keys to select the desired program number; PGM1 thru
PGM4 and press the ENTER key.
Use the UP/DOWN keys to select “Yes” to confirm and press the ENTER key.
The LCD display will show the message “Drive => Keypad, Loading...” while the
parameters are being copied and return to the program selection when finished.
(Does not restore P9.40 back to Disable Copy Keypad Function.)
Loading...
servicing.
WARNING: Do not remove the Keypad during transfer of program parameter settings to
or from the AC drive.
Chapter 3: Keypad Operation and Quickstart
DURAPULSE AC Drive User Manual
1st Ed. Rev. D 05/2013