PULSE AC Drive User Manual
A–42
GS3-FB Terminal Descriptions Wiring Notes
The control, power supply and motor leads must be laid separately. They must
not be fed through the same cable conduit / trunking.
1. Please use a shield cable to prevent interference. Do not run control wire parallel
to any high voltage AC power line (220V and up).
2. Connect shielded wire to Ground only.
3. Recommended wire size for shielded cable: AWG24 to AWG18
(0.21 to 0.81mm
2
)
4. Wire length:
Control Terminals Block Designations
FJ1
OC
5V
TP
12V
A/O
B/O
COM
VP
DCM
A
B
Connect to GS3
series control board
Wiring Terminals
Select the power
source and output
of
A
B
GS3-FB
Encoder
SW1 SW2
Please refer to instructions supplied with product for additional installation information.
Types of Encoders
Maximum
Wire Length
Wire Gauge at
Maximum Wire Length
Output Voltage 165 ft (50m)
AWG16 (1.25mm
2
) or larger
Open Collector 165 ft (50m)
Line Driver 1000 ft (300m)
Complimentary 230 ft (70m)
Terminal
Symbols
Descriptions
VP
Power source of GS3-FB (SW1 can be switched to 12V or 5V)
Output Voltage: (+12VDC ±5% 200mA) or (+5VDC ±2% 400mA)
DCM
Power source (VP) and input signal (A, B) common
A, NOT A,
B, NOT B
Input signal from Encoder. Input type is selected by SW2. Maximum 500kP/Sec
A/O, B/O
GS3-FB output signal for use with RPM Meter. (Open Collector) Maximum DC24V 100mA
COM
GS3-FB output signal (A/O, B/O) common.
PG
Pulse generator or Encoder.
IM 3~
3-Phase motor