Chapter 5: DURAPULSE MODBUS Communications
5–12
Status Monitor 2 h2101
Frequency Command F (XXX.X) h2102
Status location for the frequency setting of the AC drive.
Output Frequency H (XXX.X) h2103
Status location for the actual operating frequency present at the T1, T2, and T3
terminal.
Output Current A h2104
Status location for the output current present at the T1, T2, and T3 terminals.
DC-BUS Voltage d (XXX.X) h2105
Status location for the DC Bus Voltage.
Status Monitor 2 - Memory Address h2101
Address
Bit(s)
Bit(s) Value
Binary (Decimal)
AC Drive Status
0 and 1
00 (0) Drive operation stopped (STOP)
01 (1) Run to Stop transition
10 (2) Standby
11 (3) Drive operation running (RUN)
2 1 (4) JOG active
3 and 4
00 (0) Rotational direction forward (FWD)
01 (8) REV to FWD transition
10 (16) FWD to REV transition
11 (24) Rotational direction reverse (REV)
5 ~ 7 N/A Reserved
8 1 (32) Source of frequency determined by serial comm interface (P4.00 = 5)
9 1 (64) Source of frequency determined by AI terminal (P4.00 = 2, 3, 4 or 6)
10 1 (128) Source of operation determined by serial comm interface (P3.00 = 3 or 4)
11 1 (256) Parameters have been locked (P9.07 = 1)
12 N/A Copy command eable