3–13
Source of Frequency Command Setting: 00
Default: 01
Settings: 01 Frequency determined by digital keypad up/down
02* Frequency determined by 0 to +10V input on AI1
terminal.
03 Frequency determined by 4 to 20 mA input on AI2
terminal.
04 Frequency determined by 0 to 20 mA input on AI2
terminal.
05 Frequency determined by RS-485 communication
interface.
06 Frequency determined by -10V ~ +10V input on AI3
terminal
* In order to set P4.00 = 02, you must first change the value of P4.13 to
some value other than two (02) in order to avoid the “Error: Duplicate
Function” error message. (P4.13 default value is 02)
Electronic Thermal Overload Relay Setting: 01
Default Setting: 00
Settings: 00 Constant Torque (inverter/vector duty motor)
01 Variable Torque (fan-cooled standard motor)
02 Inactive
This function setting 01 is used to derate the AC drive output current
overload protection to protect a fan-cooled standard motor running at
low speeds.
User Defined Display Function Setting: 03
Default Setting: 00
Settings: 00 Output Frequency (Hz)
01 Motor Speed (RPM)
02 Scaled Frequency
03 Output Current (A)
04 Motor Load (%)
05 Output Voltage(V)
06 DC Bus Voltage (V)
07 PID Setpoint
08 PID Feedback (PV)
09 Frequency Setpoint
The AC drive display will default to indicate Output Current (A) when
running.
For a complete list and description of the parameters for the DURAPULSE AC drives, see
CHAPTER 4.
P8.00
P6.00
P4.00
Chapter 3: Keypad Operation and Quickstart
DURAPULSE AC Drive User Manual
1st Ed. Rev. D 05/2013