4–21
Select Method for 2nd Accel/Decel Default Setting: 00
Range: 00: Second Accel/Decel from terminal
01: Frequency Transitions P1.08 & P1.09
The second set of acceleration and deceleration times P1.05 and P1.06 can be
selected either with a multi-function input terminal programmed to Second
Accel/Decel, or by the values of the transition frequencies P1.08 and P1.09.
Accel 1 to Accel 2 Frequency Transition Default Setting: 0.0
Range: 0.0 to 400.0 Hz
This parameter sets the frequency at which the AC drive changes acceleration rate
from Acceleration Time 1 (P1.01) to Acceleration Time 2 (P1.05).
Decel 2 to Decel 1 Frequency Transition Default Setting: 0.0
Range: 0.0 to 400.0 Hz
This parameter sets the frequency at which the AC drive changes deceleration rate
from Deceleration Time 2 (P1.06) to Deceleration Time 1 (P1.02).
P1.09
Frequency
Time
Accel 1
P1.01
Accel 2
P1.05
Decel 2
P1.06
Decel 1
P1.02
Maximum Output
Frequency P0.04
Accel 1 to Accel 2
Frequency Transition
P1.08
Decel 2 to Decel 1
Frequency Transition
P1.09
Second Accel/Decel Times selected with Frequency Transition
P1.08
Frequency
Time
Multi-function
Input Terminal
On
Off
Accel 1
P1.01
Accel 2
P1.05
Decel 2
P1.06
Decel 1
P1.02
Maximum Output
Frequency P0.04
Second Accel/Decel Times selected with Multi-Function Input Terminal
P1.07
Chapter 4: AC Drive Parameters
DURAPULSE AC Drive User Manual
1st Ed. Rev. D 05/2013