2 Modbus Mapping Table
© Copyright Reserved Autonics Co., Ltd. 25
2.6.3 Communication group
No (Address) Func Explanation Setting range Notice
400151 (0096) 03/06/16 Comm. Address [ADDR] 1 to 127 -
400152 (0097) 03/06/16 Comm. Speed [BPS]
0: 24
1: 48
2: 96
3: 192
4: 384
Unit: ×100bps
400153 (0098) 03/06/16 Comm. parity bit [PRTY] 0: NONE 1: EVEN 2: ODD
-
400154 (0099) 03/06/16 Comm. stop bit [STP] 0: 1 1: 2 -
400155 (009A) 03/06/16 Response waiting time [RSwT] 05 to 99 Unit: ms
400156 (009B) 03/06/16 Comm. writing [COmW] 0: ENA 1: DISA -