EasyManuals Logo

Autonics TZN4M Instruction Manual

Autonics TZN4M
2 pages
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #2 background imageLoading...
Page #2 background image
SV setting Parameter group 1 Parameter group 2
+
3 sec
RUN mode
3 sec
3 sec
3 sec
7. Mode key
:enterparametergroup,returntoRUNmode,switchparameters,savesettingvalues
8. Auto-tuning key
: hold the key for 3 seconds to start auto-tuning. Hold the key for 5 seconds while auto-
tuning to stop auto-tuning.
9. Setting keys
:enterSVchangemode,switchelds,changevalue
( keyinthedottedlineisonlyavailableinTZN4MandTZN4Lmodels)
1. Present value (PV) display (red)
:
RUNmode:displaysthecurrentvalue(PV)
Setting mode: displays parameters
2. Set value (SV) display (green)
:
RUNmode:displaysthesetvalue(SV)
Setting mode: displays parameter setting values
3. SV2 operation indicator
: turns ON when SV2 is operating
4. Auto-tuning indicator
: turns ON when auto-tuning
5. Control output operation indicator
: turns ON when
control output is ON. Does not operate when the input
type is current output.
6. Event output indicator
: turns ON when the according
event output is ON.
( )key:Switchelds
, key: Change values
key
key
RUN mode
SV setting mode
8 9
1
3
2
5
6
4
7
Parameter groups
Parametersettingorder
Parameter group 2
Parameter group 1 SV setting
Theparametersarerelatedtoeachother.Pleasesettheparametersintheorderabove.
Whenthereisnokeyinputfor60secondswhileinSVsettingmodeorparametergroups,theunitwillreturn
to RUN mode automatically.
● SV setting
When changing the previous SV of 0
to 170
,
Thesettingeldwillblink.
Complete SV setting
Unit Description
1. SV2 temperature
YoucancontrolanadditionaltemperaturevalueatadesiredrangebyusingSV2.Connectacontactsignal(under
5VDC,250
)attheexternalterminal,tooperateintherangewherethesignalturnsON.
Set the SV2 temperature in SV2 temperature [
SU-2
] in parameter group 1.
SV
SV 2 [
SU-2
]
External terminal
(SV2IN)
ON
Temperature
Time
E.g.)Theinternaltemperatureofanelectricovenmay
drop rapidly if the door is opened while the oven
ismaintainingaspecictemperature.SetSV2
temperature [
SU-2
]toahighervaluethanSV,and
inputasignaltotheexternalterminal(SV2IN),to
quickly raise the temperature.
2. Ramp
Therampfunctioncandelaytherateoftemperaturerise/fall.IftheSVvalueischangedduringstabilizedcontrol,
the temperature of the controlled target will rise/fall during ramp up/down time [
RAPU
,
RAPD
] of parameter group
1. The ramp function activates when the power is reset or when the SV value is changed during stable control.
The ramp up/down time [
RAPU
,
RAPD
] appear only when the ramp function [
RAMP
] of parameter group 2 is
set to
ON
.
●Rampuptime[
RAPU
]
When delaying the rise of initial control
temperature or changing the SV during
stablecontrol,youcandelaytemperature
rise. Set the ramp up time [
RAPU
] longer
thanthetemperaturerisetime(tu)when
not using the ramp function.
: Not using ramp function
: Using ramp function
Changed SV
Initial SV
Time
tu tu
Ramp up time
[
RAPU
]
Ramp up time
[
RAPU
]
Temperature
●Rampdowntime[
RAPD
]
Delays declining temperature. Set the
ramp down time [
RAPD
] longer than the
temperaturedeclinetime(td)whennot
using the ramp function.
: Not using ramp function
: Using ramp function
Changed SV
Initial SV
td
Time
Ramp down time
[
RAPD
]
Temperature
Functions
Com.
speed
Cautions during Use
Major Products
RS485 Communication
ApplicableformodelsthatsupportRS485communication.Pleasereferto' Ordering Information'.
It is used to transmit PVorSV,and/orsettheSV.
Protocol BCC Communication speed 2400,4800,9600bps
Applied standard EIA RS485 Start bit 1-bitxed
Max. connections 31units(address:1to99) Data bit 8-bitxed
Communication method 2-wire half duplex Paritybit None
Synchronization method Asynchronous Stop bit 1-bitxed
Communication distance Within 1.2km
Error Dispaly
Display Description Troubleshooting
OPEN
Blinks when input is disconnected. Check input status.
HHHH
Blinks when the measured input value is higher than the temperature range.
Adjust the value to within
the temperature range.
LLLL
Blinks when the measured input value is lower than the temperature range.
Symptoms Troubleshooting
OPEN
isdisplayedonthePV
display during operation
Disconnect the power and check the input connection.
Iftheinputisconnected,disconnecttheinputwiringfromthetemperature
controllerandshortthe+and-terminals.Powerthetemperaturecontroller
and check if it displays the room temperature. If it does not display the room
temperature and continues to display
OPEN
,thecontrollerisbroken.Please
contactourtechnicalsupport.(Inputtypeisthermocouple)
Load(heater,etc.)doesnot
operate
during operation
Check the state of the control output indicator on the front panel.
Iftheindicatorisnotworking,checkparametersettings.Iftheindicatoris
working,disconnectthewiringfromtheoutputterminalofthetemperature
controllerandchecktheoutput(replaycontact,SSRdrive,current)
ERR0
(error)isdisplayedon
thePVdisplayduringoperation
Indicatesdamagetointernalchipbystrongnoise(2kVAC).
Pleasecontactourtechnicalsupport.Locatethesourceofthenoiseand
devise countermeasures.
Troubleshooting
Parameter group 2
Parameter Default Parameter Default Parameter Default
SU-2 0 P #0 IN-B 0
AL1 10 I 0 REST )0
AL2 10 D 0 RAPU 10
LBA 600 T 20 RAPD 10
AHYS 2 HYS 2 LOC OFF
Parameter Default Parameter Default Parameter Default
IN-T KCaH O-FT HEAT FS-L `00
EU-1 AL-1 UNIT ?C RAMP OFF
EU-2 AL-2 H-SC 1300 BPS 2400
AL-T AL-A L-SC `00 ADRS 01
AtT TVN1 DOT 0 LOC OFF
PIDT PIdS FS-H 1300
Parameter group 1
Factory Default
4. Auto-tuning
Auto-tuning allows the temperature controller to detect the thermal characteristics and response rates of the
controltarget.ItthencalculatesthePIDtimeconstantandsetsthevaluetoallowfastresponseratesandhigh
accuracy. Hold the key for 3 seconds during RUN mode to start auto-tuning. The auto-tuning indicator will
blink.Whenauto-tuningiscompleted,theauto-tuningindicatorwilldurnoffandthePIDtimeconstantwillbe
saved to each parameter of parameter group 1. The saved parameters can be adjusted as desired.
Tomanuallystopauto-tuning,holdthe key for 5
seconds.Whenauto-tuningisstopped,thecontroller
maintainsthePIDvaluebeforeauto-tuning.
TZN Series supports 2 auto-tuning modes.
Select TUN1 mode or TUN2 mode [
TUN1
,
TUN2
]
from auto-tuning mode [
AtT
] of parameter group 2.
Run auto-tuning during initial setup of the
temperature controller.
If the thermal characteristics of the control target
devicehaschangedafterextendedusage,re-run
auto-tuning.
3. Alarm (Event)
Alarmoutputcanbeconguredbycombiningalarmoperationandalarmoptions.Setthealarmoperationin
event 1/2 [
EU1
,
EU2
]ofparametergroup2,andsetthealarmoptionsinalarmoption[
AL-T
].
1)Alarmoperation
Mode Name Alarm operation Description
ㅁAL-0
- - Alarm output not used.
AL-1
Deviation
high-limit
alarm
SV
100
PV
110
OFF ONH
IfthedeviationofPVandSVare
higherthanthehigh-limitdeviation,
the alarm output turns ON.
High-limit deviation: 10
AL-2
Deviation
low-limit
alarm
PV
90
SV
100
OFFON H
IfthedeviationofPVandSVare
higherthanthelow-limitdeviation,
the alarm output turns ON.
Low-limit deviation: 10
AL-3
Deviation
high-limit
/low-limit
alarm
PV
90
PV
110
SV
100
OFFON ONH H
IfthedeviationofPVandSVare
higher than the high-limit deviation
orlow-limitdeviation,thealarm
output turns ON.
High-limit/low-limit deviation: 10
AL-4
Deviation
high-limit
/low-limit
reverse
alarm
PV
90
PV
110
SV
100
OFF OFFONH H
IfthedeviationofPVandSVare
higher than the high-limit deviation
orlow-limitdeviation,thealarm
output turns OFF.
High-limit/low-limit deviation: 10
AL-5
Absolute
value
high-limit
alarm
PV
90
SV
100
OFF ONH
SV
100
PV
110
OFF ONH
AlarmoutputturnsONwhenPVis
higher than the absolute value.
Absolute value alarm:
90
Absolute value alarm:
110
AL-6
Absolute
value
low-limit
alarm
PV
90
SV
100
OFFON H
SV
100
PV
110
OFFON H
AlarmoutputturnsONwhenPVis
lower than the absolute value.
Absolute value alarm:
90
Absolute value alarm:
110
SBA
Sensor
break
-
Alarm output turns ON when sensor
disconnection is detected.
LBA
Loop
break
-
Alarm output turns ON when loop
break is detected.
H: Alarm output hysteresis [
AHYS
]
Mode Name Description
AL-A
Standard
alarm
AlarmoutputturnsONuponalarmcondition,andalarmoutputturnsOFFwhen
condition is cleared.
AL-B
Alarm latch Alarm output turns ON and maintains ON upon alarm condition.
AL-C
Standby
sequence
Therstalarmconditionisignored.Itwilloperateasstandardalarmfromthesecond
alarmcondition.Ifitisunderalarmconditionwhenpowerissupplied,itwillignorethe
condition and operate as standard alarm from the next alarm condition.
AL-D
Alarm latch
and standby
sequence
It will operate as both alarm latch and standby sequence upon alarm condition. If it is
underalarmconditionwhenpowerissupplied,itwillignoretheconditionandoperate
as alarm latch from the next alarm condition.
3)Sensorbreakalarm
Alarm output turns ON when sensor is not connected or loses its connection during temperature control. Sensor
disconnection can be tested by connecting buzzers or other devices to the alarm output contact. Sensor break
alarm output operates through EV1 OUT or EV2 OUT contacts. Alarm output is disengaged after resetting the
power.
4)LoopbreakAlarm(LBA)
Diagnose control loop and transmit alarm output through temperature change of control target. During
heating(cooling)control,thealarmoutputturnsONifthePVdoesnotrise/dropbyaspecicamount(approx.2)
during LBA monitoring period [
LBA
]whilecontroloutputamountisat100%(0%).
Ifthethermalresponseofthecontroltargetisslow,theLBAmonitoringperiod[
LBA
] of parameter group 1
should be set longer.
LBAonlyoperateswhenthecontroloutputamountis100%(0%)soitcannotbeusedincurrentoutputmodels.
IfthealarmoutputturnsONafterthesensorhasbeendisconnected,thealarmoutputwillnotturnOFFeven
afterreconnectingthesensor.Todisengagethealarmoutput,thetemperaturecontrollerpowermustbereset.
TUN1
mode
[
TUN1
]
Temperature
Time
SV
Auto-tuning
TUN2
mode
[
TUN2
]
Temperature
Time
70%
SV
Auto-tuning
6. Input correction [
IN-B
]
Used to correct deviation from external devices such as temperature controllers.
E.g.)Iftheactualtemperatureis80
but the display value is 78
,settheinputcorrection[
IN-B
] value to
2
and it will display 80
as the display value.
High-
speed
response
mode
[
PIdF
]
Temperature
Time
SV
S
t
PV
Usedtominimizethetime(t)requiredtoreachtheSV.
Overshoot(S)occurs.
Used in machinery that may require warming up.
(injectionmoldingmachine,electricfurnace,etc.)
Low-
speed
response
[
PIdS
]
Temperature
Time
t
SV
PV
Usedtominimizeovershoot(S).Time(t)requiredto
reach SV may be slower.
Used for machinery or environments where overshoot
maycauseexplosionorre.(oiltemperaturecontrol,
metalplatingmachinery,etc.)
5. Dual PID control
TheresponserateofthePIDcontrolcanbeselecteddependingonthecharacteristicsofthecontroltarget.
Select high-speed response mode or low-speed response mode [
PIdF
,
PIdS
]fromPIDmethod[
PIDT
] of
parameter group 2.
PhotoelectricSensors Temperature Controllers
Fiber Optic Sensors Temperature/Humidity Transducers
Door Sensors SSRs/PowerControllers
Door Side Sensors Counters
Area Sensors Timers
ProximitySensors PanelMeters
PressureSensors Tachometer/Pulse(Rate)Meters
Rotary Encoders Display Units
Connector/Sockets Sensor Controllers
SwitchingModePowerSupplies
Control Switches/Lamps/Buzzers
I/O Terminal Blocks & Cables
Stepper Motors/Drivers/Motion Controllers
Graphic/LogicPanels
Field Network Devices
LaserMarkingSystem(Fiber,CO
,Nd:YAG)
Laser Welding/Cutting System
http://www.autonics.com
HEADQUARTERS:
18,Bansong-ro513beon-gil,Haeundae-gu,Busan,
SouthKorea,48002
TEL: 82-51-519-3232
E-mail:
sales@autonics.com
DRW170714AA
7. Manual reset [
REST
]
Whenusingproportionalcontrol(Pcontrol),thetimeoftemperature
rising time and falling time may differ depending on factors such as
the heat capacity of the control device or the heater. A certain amount
of deviation occurs even under stable conditions.
Thisdeviationisreferredtoasoffset,andcanbecongured/corrected
using manual reset [
REST
].
WhenPVandSVareequal,theresetvalueis50.0%.IfthePVis
lowerthantheSVduringstablecontrol,setthevaluetoover50.0%,
andifthePVishigherthantheSV,setthevaluetounder50.0%
Conguringmanualreset[
REST
]
according to control results.
Reset value set at under 50.0%
Reset value set at over 50.0%
Offset
Offset
SV
1.Followinstructionsin'CautionsduringUse'.Otherwise,Itmaycauseunexpectedaccidents.
2. Check the polarity of the terminals before wiring the temperature sensor.
ForRTDtemperaturesensor,wireitas3-wiretype,usingcablesinsamethicknessandlength.
Forthermocouple(CT)temperaturesensor,usethedesignatedcompensationwireforextendingwire.
3. Keep away from high voltage lines or power lines to prevent inductive noise.
Incaseinstallingpowerlineandinputsignallineclosely,uselinelterorvaristoratpowerlineandshielded
wire at input signal line.
Do not use near the equipment which generates strong magnetic force or high frequency noise.
4. Install a power switch or circuit breaker in the easily accessible place for supplying or disconnecting the
power.
5.Donotusetheunitforotherpurpose(e.g.voltmeter,ammeter),buttemperaturecontroller.
6.Whenchangingtheinputsensor,turnoffthepowerrstbeforechanging.
Afterchangingtheinputsensor,specifyinternalswitchandmodifythevalueofthecorrespondingparameter.
7. Do not overlapping communication line and power line.
Use twisted pair wire for communication line and connect ferrite bead at each end of line to reduce the effect
of external noise.
8. Make a required space around the unit for radiation of heat.
Foraccuratetemperaturemeasurement,warmuptheunitover20minafterturningonthepower.
9. Make sure that power supply voltage reaches to the rated voltage within 2 sec after supplying power.
10. Do not wire to terminals which are not used.
11. This unit may be used in the following environments.
Indoors(intheenvironmentconditionratedin'Specications')
Altitudemax.2,000m
Pollutiondegree2
Installation category II
Comprehensive Device Management Program[DAQMaster]
DAQMaster is a comprehensive device management software for setting parameters and monitoring
processes. DAQMaster can be downloaded from our website at www.autonics.com.
Item Minimumspecications
System IBMPCcompatiblecomputerwithPentium
or above
Operations Windows98/NT/XP/Vista/7/8/10
Memory 256MB+
Hard disk 1GB+ of available hard disk space
VGA Resolution: 1024×768 or higher
Others RS232Cserialport(9-pin),USBport
2)Alarmoptions
ON ON1
OFF
Unlock
ON
Lock parameter 1
( keyavailable)
ON1
Lock parameter 1
( keyunavailable)
Setting range:
1: : ( )key-Switchelds, , key-Change values
2:Pressthe key after checking or changing the values in parameter
settings to save the setting value and move to the next parameter.
Hold the key for 3 seconds anytime during parameter settings to save the
setting value and return to RUN mode.
The dotted line parameters may not appear depending on the model or
other parameter settings.
SV 2
temperature
Event 1
alarm
temp.
Event 2
alarm
temp.
LBA
monitoring
time
Alarm
output
hysteresis
Proportional
band
Integral
time
Derivative
time
Control
period
Hysteresis
Input
correction
Manual
reset
Ramp
up time
Ramp
down time
Lock
SU-2
AL1
AL2
LBA
AHYS
P
I
D
T
HYS
IN-B
REST
RAPU
RAPD
LOC
3 sec
3 sec
RUN mode
0
10
10
600
2
#0
0
0
20
2
0
)0
10
10
OFF
● Parameter group 1
2
Setting range: refer to " Input Type and Range".
Setting range: refer to " Input Type and Range".
[
AL1
,
AL2
] parameters do not appear when Event 1/2 [
EU-1
,
EU-2
] of parameter group 2 is set to
AL-0
,
LBA
,
SBA
.
[
AL2
] parameter only appears in models that support Event 2
output.
Setting range: 0 to 999 sec
Only appears when Event1/2 [
EU-1
,
EU-2
] of parameter
group 2 is set to
LBA
.
Does not appears in current output models.
Setting range: 1 to 100
/
(0.1to100.0
/
)
Does not appears when Event 1/2 [
EU-1
,
EU-2
] of parameter
group 2 is set to
AL-0
,
LBA
,
SBA
.
Setting range: 0.0 to 100.0%
ON/OFF control: Set to
)0
,PIDcontrol:Settoover
)0
OnlyappearsduringPID
control(proportionalband
[
P
] set to over
)0
).
Setting range: 1 to 100
/
(0.1to100.0
/
)
OnlyappearsduringON/OFFcontrol(proportionalband
[
P
] set to
)0
).
Setting range: -49 to 50
/
(-50.0to50.0
/
)
Setting range: 0.0 to 100%
OnlyappearswhenPcontrol(proportionalband[
P
] set to over
)0
,integraltime[
I
],andderivativetime[
D
] are set to
0
)
Setting range: 1 to 99 min
Only appears when ramp function [
RAMP
] of parameter group
2 is set to
ON
.
Settingrange:0to3,600sec
Integral operation is turned OFF
when set to
0
.
Settingrange:0to3,600sec
Derivative operation is turned
OFF when set to
0
.
Setting range: 1 to 120 sec
Set to a small value in SSR drive
outputmodels.(i.e.2sec)
PV display SV display
1
● Parameter group 2
+
3 sec
Setting range: refer to " Input Type and Range".
OFF
Unlock
ON
Lock parameter 2
Setting range:
Input type
Event 1
Event 2
Alarm
option
Auto-tuning
mode
PIDmethod
Heating/
Cooling
Temperature
unit
SV
high-limit
SV
low-limit
Decimal
point
Trans. output
high-limit
Trans. output
low-limit
Ramp
function
3 sec
RUN mode
2
Setting range: refer to " Input Type and Range".
Setting range: refer to '3. Alarm'.
Event 2 [
EU-2
] only appears in models that support Event
2 output.
Setting range: refer to '3. Alarm'.
Does not appear when Event 1/2 [
EU-1
,
EU-2
] is set to
AL-0
,
LBA
,
SBA
.
Setting range:
0
,
)0
,
)00
,
)000
Only appears with analog input.
Setting range: refer to " Input Type and Range".
OnlyappearsinmodelsthatsupportPVtransmission.
1
Com.
address
Lock
Only appears in models
that support RS485
communication
Settingrange:1to99(address)
1: : ( )key-Switchelds, , key-Change values
2:Pressthe key after checking or changing the values in parameter
settings to save the setting value and move to the next parameter.
Hold the key for 3 seconds anytime during parameter settings to save the
setting value and return to RUN mode.
The dotted line parameters may not appear depending on the model or
other parameter settings.
Pleasesetaccordingtocontrolapplication.
Do not change the settings during operation.
Itmayresultinreoraccidents.
PV display
SV display
IN-T
EU-1
EU-2
AL-T
AtT
PIDT
O-FT
UNIT
H-SC
L-SC
DOT
FS-H
FS-L
RAMP
KCaH
AL-1
AL-2
AL-A
1300
`00
0
1300
`00
2
1
ON
ON
4800 9600
BPS
ㅁㅁ ADRS
LOC
01
OFF
OFF
2400
TVN2
PIdF
COOL
?F
TVN1
PIdS
HEAT
?C

Other manuals for Autonics TZN4M

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Autonics TZN4M and is the answer not in the manual?

Autonics TZN4M Specifications

General IconGeneral
BrandAutonics
ModelTZN4M
CategoryController
LanguageEnglish

Related product manuals