11 Air heaters settings menu
PLANAR air heater settings menu:
Action of Settings menu keys:
Navigation through the menu items
Exit from this menu to the main screen
In the “heater T based” mode, the “Set temperature” of the
temperature sensor located in the heater is used for operation.
In the “control panel T based” mode, the “Set temperature” of the
temperature sensor located in the control panel is used for
operation.
In the “exterior T based” mode, the “Set temperature” of the
exterior temperature sensor is used for operation.
In the “Power based” mode, the “Set power” is used for operation.
Heater power value in the 0 to 9 range, where 0 is minimum and 9
is maximum power.
The value at which the heater will switch to standby mode. The
heater will switch from standby mode when the temperature of the
sensor used to control heater operation drops 5 °C below the “Set
temperature” value.
Ventilation mode ON setting
Ventilation mode OFF. When the heater switches to standby
mode, the air pump will shut off.
Ventilation mode ON. When the heater switches to standby
mode, the air pump will continue to operate in ventilation
mode.