Detector Settings
Addendum, AutroFlame X33AF 116-P-X33AFADDENDUM/YGB, DEC P/N 95-8624, 2007-11-12, Autronica Fire and Security AS
Page 19
15. Detector Settings
This menu shows factory settings relating to relay operation, detector
sensitivity and response.
1) Fire Relay (L/NL) Fire relay contacts, latching (L) or non-latching
(NL).
2) Fire Relay (NDE/NE) Fire relay coil, normally de-energized (NDE)
or normally energized (NE).
3) Fault Relay (L/NL) Fault relay contacts, latching (L) or non-latching
(NL).
4) Fault Relay (NDE/NE) Fault relay coil, normally de-energized
(NDE) or normally energized (NE).
5) Aux Relay (L/NL) Auxiliary relay contacts, latching (L) or non-
latching (NL).
6) Aux Relay (NDE/NE) Auxiliary relay coil, normally de-energized
(NDE) or normally energized (NE).
7) Sensitivity (VH/H/M/L) Detector sensitivity setting: Very high, High,
Medium, or Low.
8) Response (.5/3/6/9) Fire alarm processing time in seconds.