4
The 2.2K resistors are wired with the odd zones (1, 3, 5, 7), the 4.7K are wired with the even
zones (2, 4, 6, 8) as table below shows, for latest AV-2048 starting version 3.05.
Version 3.00 to 3.04
Figure 1: Optional zones wiring in AV-2048D from version 3.05 (left side)
Very Slow Response Zone
This feature entered to AV-2048D PRO Version 3.08. At 032 select the zone to act “Very Slow”,
at address 059 set the time in minutes, at 075-4 enable the “Very Slow” feature.
3. KEYPAD WIRING
Up to two AV-701T/TI or four AV-702 Keypads can be connected to AV-2004/48 Control Panel.
When few keypads are connected, wire each one directly to the panel, not from one keypad to the
other. Refer to drawing in next page.
Important Note: Up to two (2) AV-701T/TI or four (4) AV-702 Keypads can be connected to
AV-2004/48 Alarm Control Panel
When using few keypads connect them in parallel. Each keypad has four terminal wires:
(+) Power, connect to + Aux. Power
System Data, connect to OR
(–) Power, connect to – Aux. Power
System Strobe, connect to YE