18
AB-7329
<DO Terminals>
FUSE
AC24V/DC24V
+
+
+
+
-
-
LoadLoadLoadLoad
DO1
DO COM
DO2
DO(n
-
1)
DO COM
DOn
DO1
DO2
DO(n
-
1)
DOn
Internal circuit
Notes:
1. Before connecting or removing a load, turn o the power to
this product.
Failure to do so will cause malfunction of this product and
load failure.
2. The DO COMs are internally connected with each other in
the product.
However, up to 1 A can ow per common.
Figure 10. Example of DO wiring
Table 2. RJ-1102W1600 I/O terminal
Terminal
No.
Symbol Description
4 + DI CH1 +
5 – DI CH1 and CH2 common
6 + DI CH2 +
7 + DI CH3 +
8 – DI CH3 and CH4 common
9 + DI CH4 +
10 + DI CH5 +
11 – DI CH5 and CH6 common
12 + DI CH6 +
13 + DI CH7 +
14 – DI CH7 and CH8 common
15 + DI CH8 +
16 + DO CH1 +
17 – DO CH1 and CH2 common
18 + DO CH2 +
19 + DO CH3 +
20 – DO CH3 and CH4 common
21 + DO CH4 +
22 + DO CH5 +
23 – DO CH5 and CH6 common
24 + DO CH6 +
25 + DO CH7 +
26 – DO CH7 and CH8 common
27 + DO CH8 +
<UIO Terminals>
RJ-1103W0400 I/O terminal
Terminal No.
UIO
Terminal No.
UIO1 4 5 6
UIO2 13 14 15
UIO3 16 17 18
UIO4 25 26 27
Input type Voltage
+ – +
Current
+ – +
Pt100
A B B
Pt100
Pt1000
A B NC
Pt1k
DI
+ – NC
Output type Voltage
NC – +
load
Current
+ NC –
load
Symbol
A B C
It is possible to input the same two (main/aux) input
types to one terminal for voltage/current input.
The part enclosed by
is the auxiliary input of voltage/
current input.
Use the B–C terminals for the main input, and the A–B
terminals for the auxiliary input.
When using an auxiliary input, main-sub inputs are not
insulated. Provide isolators externally.