4
AB-7329
  System Conguration
In the congurations shown below, the central monitoring unit is used.
The Advanced Controller (model WJ-1103W0000) can be redundantly congured.
When it is used in a redundant conguration, the standalone type of operation is not possible.
 z Operation connected to the system
Without redundancy
Supervisory
Primary device network
Central monitoring unit*
1
Advanced Controller,
Advanced Controller for 
Chiller/Pump Units
*
2
Model WJ-110_
Third-party
BACnet
device
Remote I/O
network*
4
Switching hub
Switching hub
Switching hub Switching hub
Ethernet*
3
Ethernet (multiprotocol including BACnet/IP)
The communication distance between each device and the switching hub must be 100 m or less.
Advanced 
Remote I/O 
Module
*
5
Model
RJ-11_ _
Advanced 
Remote I/O 
Module
Model
RJ-11_ _
Advanced 
Remote I/O 
Module
Model
RJ-11_ _
Operator
Interface
*
6
Model QJ-1101
Figure 1. Example system conguration
Notes:
  *1  The Advanced Controller can be connected to an Azbil Supervisory Controller (model BH-101G0_0000) or to a third-party central 
monitoring unit using BACnet/IP communications. 
  *2  The model WJ-1103W0000 Advanced Controller, the Advanced Controller for Chiller Units, and the Advanced Controller for Pump 
Units all use BACnet/IPv4 or BACnet/IPv6. 
The model WJ-1101W000 Advanced Controller uses BACnet/IPv4 only. 
The IPv6 specication is based on BACnet-2012 (which conforms to the Institute of Electrical Installation Engineers of Japan’s 
IEIEJ-G-D006:2017 standard) with ANNEX U of BACnet-2016.
  *3  A network that connects an Advanced Controller (model WJ-1101W000 or WJ-1103W000), Advanced Controller for Chiller Units, 
or Advanced Controller for Pump Units with the products that are under its control is referred to as a local I/O network.  
A switching hub is not required for the local I/O network since daisy chain Ethernet is used between the Advanced Controller and 
the products under its control, as well as between those products.
  *4  A network that connects an Advanced Remote I/O Module to a host network is referred to as a remote I/O network. 
To connect this product to a remote I/O network, a switching hub is required. 
The maximum number of the Advanced Remote I/O Modules connected to the remote I/O network is 3 per Advanced Controller 
(model WJ-1101W000 or WJ-1103W000), Advanced Controller for Chiller Units, or Advanced Controller for Pump Units. 
When using IPv6 for BACnet communication, Advanced Remote I/O Modules cannot be connected via a remote I/O network.
  *5  A maximum of 20 Advanced Remote I/O Modules can be connected to an Advanced Controller (model WJ-1101W000 or 
WJ-1103W000), Advanced Controller for Chiller Units, or Advanced Controller for Pump Units. This gure is the sum of the units 
connected to the local and remote I/O networks.
  *6  The Operator Interface (model number QJ-1101) can manage a maximum of four controllers (model number WJ-1102_ and 
WJ-1103W000).