Spray-gun cleaner Starter Page 13
equipment and facility engineering
Exhaust
The waste air hose must lead outside. One has to
ensure that the fumes are not led into areas where
people are likely to be. The waste air has to be
exhausted safely. This means that it has not to be
fed into chimneys serving furnaces or fireplaces and
not into exhaust channels of spraying and drying
cabinets
Compressed air connection
One compressed air connection has to be provided
by the plant, depending on the machine:
Operating pressure max : 600 kPa (6 bar ; 87 psi)
Operating pressure min. : 500 kPa (5 bar ; 73 psi)
A pressure-regulating valve has to be used if the compressed air connections do not
have the required operating pressures. Use only dry and oil-free air!!
Grounding: Device has a grounding cable!
In the proximity of the pumps there is a grounding cable, which has to be
grounded safely by a qualified person (e.g. electricians).
Customer-provided solvent tanks must be grounded separately!
After proper installation and connection to the compressed air supply, the cleaning unit can be
commissioned.
Unnecessary dry running of the membrane pumps should be avoided.
Do not open the door when the automatic wash cycle is running.
If necessary, turn the timer to "0".
Attention! Only use original B-TEC
waste air hoses. Risk of fire if
other hoses are used.
Compressed air connection
50.20.05